| For remote Failure description | Reason | Remarks | |
| type, flash |
|
|
|
| times |
|
|
|
1 | Indoor ambient temp. sensor failure | Sensor broken down or short circuit for more than 2m continuously |
| |
2 | Indoor coil temp. sensor failure | Sensor broken down or short circuit for more than 2m continuously |
| |
3 | Outdoor ambient temp. sensor failure | Sensor broken down or short circuit for more than 2m continuously |
| |
4 | Outdoor coil temp. sensor failure | Sensor broken down or short circuit for more than 2m continuously |
| |
|
|
|
|
|
5 | CT check abnormal 3 times in 30m |
| ||
6 | High pressure abnormal | High pressure switch acts 3 times in 30m |
| |
7 | Power supply abnormal | Fault phase, short of phase, out of balance greatly |
| |
|
| Communication between wired |
|
|
8 | controller and indoor abnormal | Communication abnormal for more than 4m continuously |
| |
9 | Communication between indoor and outdoor abnormal | Communication abnormal for more than 4m continuously |
| |
10 | Drainage system abnormal | Float switch broken down for more than 25m continuously |
| |
11 | Outside alarm signal input | Outside signal broken down for more than 10s |
| |
12 | Gas pipe temp. sensor abnormal | Sensor broken down or short circuit for more than 2m continuously |
| |
13 | Temperature protection malfunction | Solenoid valve act incorrectly 3 times continuously |
| |
14 | Discharging temp. sensor abnormal | Sensor broken down or short circuit for more than 2m continuously |
| |
15 | EEPROM abnormal | EEPROM data missing |
| |
16 | Pressure abnormal(low pressure) | Low pressure switch acts in normal running |
| |
|
|
|
| Resumable if |
17 | Compressor overheat | The discharging temperature is higher than 120degree | lower than 100 | |
degree | ||||
18 | Abnormal mode | Indoor operation mode is different with the running indoor unit. |
|
19Outdoor coil B(suction temp
20Outdoor discharging B(oil temp
shows resumable fault, * shows it is not resumable fault.