Haier AC142ACEAA, AC182ACEAA Connecting the Piping, Install the Drain Hose, Flare Processing

Page 14

Installation Procedures

5.INSTALL THE DRAIN HOSE

Select whether the drain hose will be connected to the left or right side.(Fig.3)

Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.6)

Wrap the insulation (drain hose)around the drain hose connection.(Fig.7)

Be sure to arrange the drain hose correctly so that it is leveled lower than the drain hose connecting port of the indoor unit.(Fig.18)

Fig. 18

Remove the hole cover.

Arrange the drain hose

 

 

 

 

Drain hose

 

 

 

 

 

 

 

 

 

lower than this portion

 

 

 

 

 

OK

OUTDOOR UNIT INSTALLATION

CONNECTING THE PIPING

1.FLARE PROCESSING

(1)Cut the connection pipe with pipe cutters so that the pipe is not deformed.

(2)Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs.

(3)Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in (Table1) and insert the flare nut onto the pipe, and flare with a flaring tool.

(4)Check if the flared part "L" (Fig.20)is spread uniformly and that there are no cracks.

 

Table 1

 

 

Pipe

Flare nut

 

 

Small pipe

Small (width across flats 22mm)

 

 

Large pipe

Large (width across flats 24mm)

 

 

NO

Fig. 19

Piping hole

 

Base (Bottom)

VT wire hole

Intake grill

Pass the drain hose through here

Cut the grill

VT wire

Drain hose

Fig. 20

Width across flats

 

 

L dimension

 

L

 

 

 

 

Diameter of pipe Dimension A (mm)

For series 142, 182

Liquid pipe

6.35mm (1/4”)

1.0~1.2

Gas pipe

12.7mm (1/2”)

 

 

For series 242

Liquid pipe

9.52mm (3/8”)

 

Gas pipe

15.88mm (5/8”)

1.4~2.2

 

 

2. BENDING PIPES

The pipes are shaped by your hands. Be careful not to collapse them.

Fig. 21

OK

NO

Extend the pipe by unwinding it

12

Image 14
Contents Operation & Installation Manual Contents Disposal of the old air conditioner WB C Maximum Minimum IndoorDB C DB C WB CSafety Precautions Name of Parts Indoor UnitCleaning and Care Cleaning the Air FilterPiping hole cover Operation TipsDrain hose Installation LocationInstallation Procedures Selecting the Mounting PositionDrilling for Piping Preparing Indoor Unit InstallationFloor Console Type Wall 6mm Rear 7cm Right Indoor unitDrain pan Nylon fastener Drain hose Installing Drain HoseUnder Ceiling Type Drain pan Drain hose Insulation Drain hoseWall Installing BracketsSelect piping and drain directions With a concrete drill, drill four 12.7 mm dia. HolesFlare Processing Connecting the PipingInstall the Drain Hose Insulation Round terminalElectrical Requirement Electrical WiringIndoor Unit Side Check Items Electrical WiringMount the Cover Plate Intake Grill Customer GuidanceMount the intake grill Trouble Shooting Followings are not problemsPoor cooling or heating Error display For *.ERA Error display For *.EAA Haier Group