Installation Manual For Indoor Unit

Installing the suspension screw:

Use M8 or M10 suspension screws (4,prepared in the field)(when the suspension screw height exceeds 0.9m,M10 size is the only choice).These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.

Wooden structure

A square wood shall be supported by the beams and then set the suspension screws.

New concrete slab

To set with embedded parts,foundation bolts etc.

Square wood Beam

Suspension screw

 

 

Iron reinforcement

 

 

Foundation bolt

Knife embedded part

Guide plate embedded part

Pipe suspension foundation bolt

Original concrete slad

Use hole hinge,hole plunger or hole bolt.

Steel reinforcement structure

Use steel angle or new support steel angle directly.

Hanging bolt

Suspension screw

Support steel angle

Hanging of the indoor unit

Fasten the nut on the suspension screw and then hang the suspension screw in the T slot of the suspension part of the unit.

Aided with a level meter,adjust level of the unit within 5mm2

28

Image 29
Contents Duct Type AIR Conditioner Table of Contents Disposal of the old air conditioner Make sure the system is grounded Safety PrecautionsDo not wash the air conditioner with water Cooling Rated Maximum Minimum IndoorOutdoor Heating IndoorParts and Functions Parts and Functions Operation Power ON/OFFCool Fan operation Auto RUN, COOL,HEAT and DRY operation 2TIMER mode selection 1After unit start, select your desired operation mode3Timer setting 4Confirming your setting3Time setting for Timer on Press Timer button to change Timer modeTime confirming for Timer on 5Time setting for Timer OFFCooling, dehumidifying mode Heating mode This series changeover switch is set 1. on 2.OFF 3.OFF 4.OFF Unit fails to start MalfunctionMalfunction Followings are not malfunction Points to observe Care and MalntenanceFor Preparation of HeatingHot Keep When heating is startedInstallation place Is The Unit Installed CorrectlyInstall wire controller Installation Manual For Wire ControllerIndoor unit wiring Safety precautions Installation Manual For Indoor UnitIndoor unit Installation Manual For Indoor Unit Sketch map of long duct Thermal insulation of duct Installation of air sending ductInstallation of air return duct Foundation bolt Hose RequirementsPipe and insulation material Connection of refrigerant pipe Allowable pipe length and drop Pipe material and sizeSupplementary refrigerant Gas leakage detection Vacuum pumpingOpen all valves Electric wiring Haier Group