Haier HDU-18CF03 Allowable pipe length and drop Pipe material and size, Supplementary refrigerant

Page 31

Installation Manual For Indoor Unit

! Caution

In installation, if there is refrigerant gas leakage, please take ventilation measures immediately. The refrigerant gas will generate poisonous gas upon contacting fire.

After installation, please verify that there is no refrigerant leakage. The leaked refrigerant gas will produce poisonous gas when meeting fire source such as heater and furnace etc.

Allowable pipe length and drop

These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.

Pipe material and size

Pipe material

Phosphorus deoxidized copper seamless pipe (TP2) for air conditioner

 

 

 

 

 

Gas side

ÿ12.70

HDU-18CF03

Pipe size

Liquid side

ÿ6.35

HDU-18HF03

(mm)

 

 

 

Gas side

ÿ15.88

HDU-28CF03

 

 

Liquid side

ÿ9.52

HDU-28HF03

Supplementary refrigerant

The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit R22

The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant.

Requirement

Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.

Connection of refrigerant pipe

Conduct flared connection work to connect all refrigerant pipes.

The connection of indoor unit pipes must use double spanners. The installing torque shall be as given in the following table.

Connecting pipe

Installing torque

O.D.(mm)

(N-m)

ÿ6.35

11.8 (1.2kgf-m)

ÿ12.70

49.0 (5.0 kgf-m)

ÿ9.52

24.5 (2.5kgf-m)

ÿ15.88

78.4 (8.0 kgf-m)

 

 

Double-spanner operation

30

Image 31
Contents Duct Type AIR Conditioner Table of Contents Disposal of the old air conditioner Make sure the system is grounded Safety PrecautionsDo not wash the air conditioner with water Heating Indoor Rated Maximum Minimum IndoorCooling OutdoorParts and Functions Parts and Functions Operation Power ON/OFFCool Fan operation Auto RUN, COOL,HEAT and DRY operation 4Confirming your setting 1After unit start, select your desired operation mode2TIMER mode selection 3Timer setting5Time setting for Timer OFF Press Timer button to change Timer mode3Time setting for Timer on Time confirming for Timer onCooling, dehumidifying mode Heating mode This series changeover switch is set 1. on 2.OFF 3.OFF 4.OFF Unit fails to start MalfunctionMalfunction Followings are not malfunction Points to observe Care and MalntenanceFor Preparation of HeatingHot Keep When heating is startedInstallation place Is The Unit Installed CorrectlyInstall wire controller Installation Manual For Wire ControllerIndoor unit wiring Safety precautions Installation Manual For Indoor UnitIndoor unit Installation Manual For Indoor Unit Sketch map of long duct Installation of air return duct Installation of air sending ductThermal insulation of duct Foundation bolt Pipe and insulation material RequirementsHose Supplementary refrigerant Allowable pipe length and drop Pipe material and sizeConnection of refrigerant pipe Open all valves Vacuum pumpingGas leakage detection Electric wiring Haier Group