HSU-12HS03/R2(DB)

 

 

 

 

 

 

 

 

 

Domestic Air Conditioner

Models: HSU-09HS03/R2(DB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and medium of wind volume when it is under heating mode. Modification index table for set temperature

Mode

Content of modification

Modified variable

Modified parameter

 

 

 

 

Heating

Operation mode modi hp

ETBL0

 

 

fication

 

 

 

 

 

 

 

Forceful operation modification

ETBL1

 

 

 

 

 

 

Weak wind volume

ETBL2

 

 

modification

 

 

 

 

 

 

 

Medium wind volume

ETBL3

 

 

modification

 

 

 

 

 

 

Cooling &

Operation mode modification

ETBL4

 

moisture

 

 

 

Forceful operation modification

ETBL5

 

removing

 

 

 

 

 

 

 

2.4temperature level control 2.4.1 Deviation

Work out the deviation of temperature level as follows:

In heating mode: E=(Remote -control set temperature+ modified value)-room temperature

In cooling & moisture removing mode: E= room temperature -(Remote-control set temperature + modified value)

2.4.2 Compressor OFF

E is minus and E>ΔT

 

Heating

 

Cooling

 

 

 

 

 

ΔT

TCHAHL

 

TCHACL

 

afterΔT changes

TCHAHH

 

TCHACH

 

condition forΔT changes

 

 

 

 

 

 

 

 

 

The compressor stops after 120 seconds of continuous detection

When the operation starts,according to the table above, the unit will operate according to the after-the-ΔT-change parameters before the compressor stops for the first time.

From the time the compressor stops to the time it starts again, the operation will follow the ΔT (except the moisture removing mode)

When the operation starts and the operation modes change (except when the idle mode is over) and the deviation is bigger than ΔT, the compressor starts.

When the compressor is working and the remote -controller set temperature falls below ΔT, the compressor stops.

2.4.3 Compressor operation

When the compressor is kept idle for 3 minutes, the deviation E will be higher than -T+0.67and the compressor will start working.

2.4.4 DASH operation

When the operation starts or the operation mode changes (except when the compressor is switched on after being off), the compressor is on and the indicated maximum frequency should be as follows:

24

Image 24
Contents Domestic Air Conditioner Models Content Description Product Model Coding Series Introduction Introductory Remarks Standard Situation/Conditions Specifications Specification 2700950-3400W Curves of performance of compressor Curent a Input W Input Power Domestic Air Conditioner Outdoor unit NE T Dime Nsions for Indoor Unit Knock-down drawings Domestic Air Conditioner Domestic Air Conditioner Model HSU-12HS03/R2DB KNOCK-DOWN Drawings for Outdoor UNITHSU-09/12HS03/R2DB No. Spare parts Spare parts description in english Model QTY Brief introduction to electrical Control functions Indoor Unit Part Tchahl Tchacl Silent Fqshot Heating Moisture Fqdry Removing Cooling SLO Frequency control form for wind volume THHOT1 Refer to the temperature level control function Domestic Air Conditioner THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0 Trouble Records Outdoor Unit Part . Conditions to enter into the defrosting stage Domestic Air Conditioner Domestic Air Conditioner Wiring diagram Indoor Unit Diagram Wiring Diagram of Outdoor Unit Circuit Diagram Indoor Unit Outdoor Unit Abnormity Diagnose Or Unit Part Overheat .The system is lack Eeprom LED Trouble Shooting Domestic Air Conditioner Refrigerating Cycle Diagram Refrigerating cycle diagram Noise level test chart and air velocity distribution Noise level test chart Air velocity distribution Installation manual Installation Manual of Room Air Conditioner Power Source Making a Hole on the Wall and Fitting the Piping Hole Cover Installation of the Indoor Unit Drawing of pipe Indoor unit Outdoor unit Outdoor Unit Outdoor Unit On Drainage Sincere Forever