Haier HSU-09HS03/R2DB, HSU-12HS03/R2DB THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0

Page 32
High Work-intense

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

according to the heat-exchange temperatures as shown in the table below. High Work-intense protection control:

Picture 12.1

Heat-exchange temperature

frequency values when the high work-intense starts

THHEAT6 74.7

THHEAT5 70.3

THHEAT4 65.1

THHEAT3 62.2

THHEAT2 52.9

THHEAT1 51.6

THHEAT0 47.1

Indicated

frequency

 

C D E

D C B

A

B C D E

Normal

idle mode

 

 

stop

High Work-intense protection

High Work-intense protection

alarm

.protection alarm will start if there are two times of high work-intense protection within 30 minutes.

. If the heat-exchange temperature does not reach THHEAT [2], it will resume to the normal temperature level control

. The smaller one of the high work-intense frequency and level frequency will be the operation data.

11.Low-temperture treatment for Heating mode

If the four-way valve can not switch or when the none-frost-removing compressor starts again under the heating mode if the heat-exchange temperature remains under"THHOTLTH"-4.5℃)for 90 seconds, the compressor will start 3 minutes of idle mode and start again when the heat-exchange temperature is above " THHOTLTH "-4.5℃)

12. Remote control

. Start or stop running with the remote-control signals.

. Only OFF signal is accepted when there are emergencies or malfunctions.

1 second delay: Starting, stopping and signals except the wind direction signal all begins 1 second after the receiption of the signal.

13.EEPROM control

. EEPROM is wrong when the EEPROM parameter sum does not accord with the check sum after the outdoor unit is powered on.

. The outdoor unit EEPROM is wrong will be displayed when the indoor unit

32

Image 32
Contents Domestic Air Conditioner Models Content Description Product Model Coding Series Introduction Introductory Remarks Standard Situation/Conditions Specifications Specification 2700950-3400W Curves of performance of compressor Curent a Input W Input Power Domestic Air Conditioner Outdoor unit NE T Dime Nsions for Indoor Unit Knock-down drawings Domestic Air Conditioner Domestic Air Conditioner Model HSU-12HS03/R2DB KNOCK-DOWN Drawings for Outdoor UNITHSU-09/12HS03/R2DB No. Spare parts Spare parts description in english Model QTY Brief introduction to electrical Control functions Indoor Unit Part Tchahl Tchacl Silent Fqshot Heating Moisture Fqdry Removing Cooling SLO Frequency control form for wind volume THHOT1 Refer to the temperature level control function Domestic Air Conditioner THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0 Trouble Records Outdoor Unit Part . Conditions to enter into the defrosting stage Domestic Air Conditioner Domestic Air Conditioner Wiring diagram Indoor Unit Diagram Wiring Diagram of Outdoor Unit Circuit Diagram Indoor Unit Outdoor Unit Abnormity Diagnose Or Unit Part Overheat .The system is lack Eeprom LED Trouble Shooting Domestic Air Conditioner Refrigerating Cycle Diagram Refrigerating cycle diagram Noise level test chart and air velocity distribution Noise level test chart Air velocity distribution Installation manual Installation Manual of Room Air Conditioner Power Source Making a Hole on the Wall and Fitting the Piping Hole Cover Installation of the Indoor Unit Drawing of pipe Indoor unit Outdoor unit Outdoor Unit Outdoor Unit On Drainage Sincere Forever