Haier HSU-09HS03/R2DB, HSU-12HS03/R2DB service manual Outdoor Unit

Page 62

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

Outdoor Unit

1 Installation of Outdoor Unit

Install according to Drawing for the installation of indoor and outdoor units

2 Connection of Pipes

To bend a pipe, give the roundness as large as possible not to crush the pipe, and the bending radius should be 30 to 40 mm or longer.

Connecting the pipe of gas side first make working easier.

The connection pipe is specialized for R410A.

The max length of connection pipe of 12 series is 15m and the max length of 07,09 series is 7m. The max vertical distance between the indoor unit and the outdoor unit is 5m

Half union

 

 

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spanner

Torque wrench

Forced fastening without careful centering may damage the threads and cause a leakage of gas.

Pipe Diameter( )

Fastening Torque

 

 

 

Liquid Side 6.35mm(1/4")

18N.m

 

 

Gas Side 6.35mm(3/8")

42N.m

 

 

Gas Side 12.7mm(1/2")

55N.m

 

 

 

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

The standard pipe length is 5m, If it is over 5m, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 20g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant.

3 Connection

Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into terminal block, then tighten the screws

Insert the cable according to terminal number in the same manner as the indoor unit.

4 Attaching Drain-Elbow

If the drain-elbow is used, please attach it as figure.

Note: Only for heat pump unit.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

Fix the cable with a clamp.

Drain hose

62

Image 62
Contents Domestic Air Conditioner Models Content Description Product Model Coding Series Introduction Introductory Remarks Standard Situation/Conditions Specifications Specification 2700950-3400W Curves of performance of compressor Curent a Input W Input Power Domestic Air Conditioner Outdoor unit NE T Dime Nsions for Indoor Unit Knock-down drawings Domestic Air Conditioner Domestic Air Conditioner Model HSU-12HS03/R2DB KNOCK-DOWN Drawings for Outdoor UNITHSU-09/12HS03/R2DB No. Spare parts Spare parts description in english Model QTY Brief introduction to electrical Control functions Indoor Unit Part Tchahl Tchacl Silent Fqshot Heating Moisture Fqdry Removing Cooling SLO Frequency control form for wind volume THHOT1 Refer to the temperature level control function Domestic Air Conditioner THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0 Trouble Records Outdoor Unit Part . Conditions to enter into the defrosting stage Domestic Air Conditioner Domestic Air Conditioner Wiring diagram Indoor Unit Diagram Wiring Diagram of Outdoor Unit Circuit Diagram Indoor Unit Outdoor Unit Abnormity Diagnose Or Unit Part Overheat .The system is lack Eeprom LED Trouble Shooting Domestic Air Conditioner Refrigerating Cycle Diagram Refrigerating cycle diagram Noise level test chart and air velocity distribution Noise level test chart Air velocity distribution Installation manual Installation Manual of Room Air Conditioner Power Source Making a Hole on the Wall and Fitting the Piping Hole Cover Installation of the Indoor Unit Drawing of pipe Indoor unit Outdoor unit Outdoor Unit Outdoor Unit On Drainage Sincere Forever