Haier HSU-09HS03/R2DB, HSU-12HS03/R2DB service manual Outdoor Unit Part

Page 34

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

OUTDOOR UNIT PART

Chapter I: Indoor Unit and Main board for Outdoor Unit

Notice:

During operations under any mode, if short circuit, open circuit and other malfunctions of the temperature sensors are detected, the main engine should come to a halt immediately.

1. Outdoor-board:

1.1.Forced cooling operation switch:

Short circuit this switch before electrifying, data communication to indoor unit will be ignored:

Forced cooling will function, the 3-minute delay will be cancelled, and the following output will be ON simultaneously:

High wind volume (H) for outdoor fan motor; Compressor operates at the frequency of 80Hz.

1.2.Forced heating operation switch:

Short circuit this switch before electrifying, data communication to indoor unit will be ignored:

Forced heating will function, the 3-minute delay will be cancelled, and the following output will be ON simultaneously:

High wind volume (H) for outdoor fan motor; Compressor operates at the frequency of 80Hz. CPU checks all A/D ports

BWhen safeguarding action happens outdoors, the actions in A should be OFF, and other inputs are independent of the actions in A.

CLED output: Goes along even if safeguarding action happens outdoors; Cut this switch and go back to the original state. (The out-door safeguarding action will continue)

Chapter II: Basic Functions

3. Cooling mode

3.1.The four-way valve does not work (not electrified)

3.2.The discharge temperature sensor will not be tested within five minutes after the compressor is started

3.3.Outdoor fan motor control: The fan motor starts five seconds after the compressor starts, switching conditions for the two gears of wind volume are

as follows:

 

T ambient temp. <21

, Low wind volume

 

 

 

 

 

 

 

 

T

ambient

temp.

>21 , High wind

volume

 

 

When the fan motor starts up, and

the ambient temperature is at the return difference ( 2

), it runs at the low

 

 

 

 

 

± ℃

 

wind volume.

 

 

 

 

 

 

 

3.4.Compressor control: Frequency range: 30HZ---------

120HZ

frequency is

 

T ambient temp. <16

, the maximum

65HZ

16

 

 

30

the maximum

℃≤

T ambient temp.

 

 

 

 

≤ ℃,

frequency is 90HZ

T ambient temp. 41

 

the maximum frequency is

30

 

 

℃≤

 

℃,

 

 

110HZ

 

 

 

 

 

 

 

 

℃,

 

 

 

 

T ambient temp.

41

the maximum frequency is 85HZ

Actual temperature and frequency maybe adjusted through EEPROM

34

Image 34
Contents Domestic Air Conditioner Models Content Description Product Model Coding Series Introduction Introductory Remarks Standard Situation/Conditions Specifications Specification 2700950-3400W Curves of performance of compressor Curent a Input W Input Power Domestic Air Conditioner Outdoor unit NE T Dime Nsions for Indoor Unit Knock-down drawings Domestic Air Conditioner Domestic Air Conditioner Model HSU-12HS03/R2DB KNOCK-DOWN Drawings for Outdoor UNITHSU-09/12HS03/R2DB No. Spare parts Spare parts description in english Model QTY Brief introduction to electrical Control functions Indoor Unit Part Tchahl Tchacl Silent Fqshot Heating Moisture Fqdry Removing Cooling SLO Frequency control form for wind volume THHOT1 Refer to the temperature level control function Domestic Air Conditioner THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0 Trouble Records Outdoor Unit Part . Conditions to enter into the defrosting stage Domestic Air Conditioner Domestic Air Conditioner Wiring diagram Indoor Unit Diagram Wiring Diagram of Outdoor Unit Circuit Diagram Indoor Unit Outdoor Unit Abnormity Diagnose Or Unit Part Overheat .The system is lack Eeprom LED Trouble Shooting Domestic Air Conditioner Refrigerating Cycle Diagram Refrigerating cycle diagram Noise level test chart and air velocity distribution Noise level test chart Air velocity distribution Installation manual Installation Manual of Room Air Conditioner Power Source Making a Hole on the Wall and Fitting the Piping Hole Cover Installation of the Indoor Unit Drawing of pipe Indoor unit Outdoor unit Outdoor Unit Outdoor Unit On Drainage Sincere Forever