Haier HSU-12HS03/R2DB, HSU-09HS03/R2DB service manual Domestic Air Conditioner

Page 37
outdoor coil52, the
outdoor coil52, the

Domestic Air Conditioner

HSU-12HS03/R2(DB)

Model: HSU-09HS03/R2(DB)

and the outdoor fan motor returns to its original state;

The above temperature points, frequency-decreasing step and time interval can all be adjusted through EEPROM

III.Anti over-loading operation while heating:

5.3.When the operation frequency F40HZ, if the temperature of the outdoor

coiled pipe T outdoor coil52, the outdoor fan motor performs forced high-speed operation and the operation frequency of the compressor should be decreased by 2Hzthen examine the temperature of the outdoor coiled pipe at 10-second intervals, if T outdoor coil52, decrease the operation frequency further by 2Hzuntil the frequency is the lowest;

During the frequency-decreasing operation, if 47℃≤T compressor and the fan motor keep their original states;

When T outdoor coil46, the compressor runs at the normal operating frequency, and the outdoor fan motor returns to its original state;

5.4.When the operation frequency F40HZ, if the temperature of the outdoor coiled pipe T outdoor coil57, the outdoor fan motor performs forced high-speed operation and the operation frequency of the compressor should be decreased by 2Hzthen examine the temperature of the outdoor coiled pipe at 10-second intervals, if T outdoor coil57, decrease the operation frequency further by 2Hzuntil the frequency is the lowest;

During the frequency-decreasing operation, if 52℃≤T compressor and the fan motor keep their original states

When T outdoor coil51, the compressor runs at the normal operating frequency, and the outdoor fan motor returns to its original state;

The above temperature points, frequency-decreasing step and time interval can all be adjusted through EEPROM

6.. Compressor discharge safeguard:

5 minutes after the compressor starts, when the compressor temperature rises above 105, decrease the compressor frequency by 2HZ/stop for 10 seconds, until the compressor temperature falls below 90, the compressor returns to normal operation;

When the compressor temperature rises above 115, the compressor should stop at once, wait until the compressor temperature falls below 90and the waiting time period exceeds 3 minutes, the compressor returns to normal operation;

After the compressor restarts, if the compressor temperature rises above 115once more within 15 minutes, the compressor should stop at once and give an alarm.

The temperature points are stored in EEPROM

37

Image 37
Contents Domestic Air Conditioner Models Content Description Product Model Coding Series Introduction Introductory Remarks Standard Situation/Conditions Specifications Specification 2700950-3400W Curves of performance of compressor Curent a Input W Input Power Domestic Air Conditioner Outdoor unit NE T Dime Nsions for Indoor Unit Knock-down drawings Domestic Air Conditioner Domestic Air Conditioner Model HSU-12HS03/R2DB KNOCK-DOWN Drawings for Outdoor UNITHSU-09/12HS03/R2DB No. Spare parts Spare parts description in english Model QTY Brief introduction to electrical Control functions Indoor Unit Part Tchahl Tchacl Silent Fqshot Heating Moisture Fqdry Removing Cooling SLO Frequency control form for wind volume THHOT1 Refer to the temperature level control function Domestic Air Conditioner THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 THHEAT6 THHEAT5 THHEAT4 THHEAT3 THHEAT2 THHEAT1 THHEAT0 Trouble Records Outdoor Unit Part . Conditions to enter into the defrosting stage Domestic Air Conditioner Domestic Air Conditioner Wiring diagram Indoor Unit Diagram Wiring Diagram of Outdoor Unit Circuit Diagram Indoor Unit Outdoor Unit Abnormity Diagnose Or Unit Part Overheat .The system is lack Eeprom LED Trouble Shooting Domestic Air Conditioner Refrigerating Cycle Diagram Refrigerating cycle diagram Noise level test chart and air velocity distribution Noise level test chart Air velocity distribution Installation manual Installation Manual of Room Air Conditioner Power Source Making a Hole on the Wall and Fitting the Piping Hole Cover Installation of the Indoor Unit Drawing of pipe Indoor unit Outdoor unit Outdoor Unit Outdoor Unit On Drainage Sincere Forever