Goodman Mfg CPG SERIES installation manual Clearances

Page 5

The base should also be located where no runoff of water from higher ground can collect in the unit.

ROOF TOP INSTALLATIONS ONLY:

To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.

The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material.

To avoid possible personal injury, a safe, flat surface for service personnel should be provided.

As indicated on the unit data plate, a minimum clearance of 36” to any combustible material is required on the furnance access side of the unit. All combustible materials must be kept out of this area.

This 36” clearance must also be maintained to insure proper combustion air and flue gas flow. The combustion air intake and furance flue discharge must not be blocked for any reason, including blockage by snow.

Adequate clearances from the furnace flue discharge to any adjacent public walkways, adjacent buildings, building openings or openable windows must be maintained in accordance with the latest edition of the National Fuel Gas Code (ANSI Z223.1)

Minimum horizontal clearance of 48” from the furnace flue discharge to any electric meters, gas meters, regulators and relief equipment is required.

UNIT PRECAUTIONS

Do not stand or walk on the unit.

Do not drill holes anywhere in panels or in the base frame of the unit. Unit access panels provide structural support.

Do not remove any access panels until unit has been installed on roof curb or field supplied structure.

Do not roll unit across finished roof without prior approval of owner or achitect.

Do not skid or slide on any surface as this may damage unit base. The unit must be stored on a flat, level surface. Protect the condenser coil because it is easily damaged.

ROOF CURB INSTALLATIONS ONLY:

Curb installatons must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association.

Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.

Full perimeter roof curbs are available from the factory and are shipped unassembled. Field assembly, squaring, level- ing and mounting on the roof structure are the responsibility of the installing contractor. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory.

WARNING

TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.

Sufficient structural support must be determined prior to locating and mounting the curb and package unit.

Ductwork must be constructed using industry guidelines. The duct work must be placed into the roof curb before mounting the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered type curbs are not available from the factory.

Curb insulation, cant strips, flashing and general

roofing material are furnished by the contractor.

The curbs must be supported on parallel sides by roof mem- bers. The roof members must not penetrate supply and re- turn duct opening areas as damage to the unit might occur.

NOTE: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installaton after unit placement is not recommended.

CAUTION

ALL CURBS LOOK SIMILAR. TO AVOID INCORRECT CURB POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY. INSTRUCTIONS MAY VARY IN CURB STYLES AND SUPERSEDES INFORMATION SHOWN.

See the manual shipped with the roof curb for assembly and installation instructions.

CLEARANCES

48”

48”

75”

Unit Clearances

5

Image 5
Contents CPG Series Safety Instructions Replacement PartsHigh Voltage General InformationUnit Location Clearances Roof TOP Duct Connections Roof Curb POST-INSTALLATION ChecksRigging Details Weights shown are belt drive with no accessories Power and Low Voltage Block Connections Electrical WiringAreas Without Convenience Outlet GAS Supply PipingInlet GAS Pressure GAS Piping Checks Propane GAS InstallationsVenting Condensate Drain Connection Circulating AIR and FiltersPRE-STARTUP Instructions STARTUP, ADJUSTMENTS, and ChecksPercent voltage unbalance Must not exceed 2% Three Phase Models OnlyRollout Protection Control Manifold Pressure Check PSC Motor Flame Sensor and Ignition Electrode Location Normal Sequence of OperationCheck rollout limit TroubleshootingInput Btu/Hr = AdjustmentInput Rating Motor Sheave Adjustments AIR Flow AdjustmentsMaintenance PSC MotorCabinet Finish Maintenance Burner Flame CPG036 Direct Drive Horizontal CPG036 Direct Drive Down ShotCPG048 Direct Drive Horizontal CPG048 Direct Drive Down ShotCPG060 Direct Drive Down Shot CPG060 Direct Drive Horizontal CPG048 Standard Belt Drive Horizontal CPG036 Standard Belt Drive HorizontalCPG060 Standard Belt Drive Horizontal CPG072 Standard Belt Drive Horizontal806 744 CPG048 High Static Belt Drive Down Shot CPG036 High Static Belt Drive Down ShotCPG060 High Static Belt Drive Down Shot CPG072 High Static Belt Drive Down ShotCPG048 High Static Belt Drive Horizontal CPG036 High Static Belt Drive HorizontalCPG060 High Static Belt Drive Horizontal CPG072 High Static Belt Drive HorizontalAppendix B Electrical Data Appendix C Unit Dimensions Appendix D Wiring Diagrams IIC CPG036480451D Single Phase 240V/60HZ Direct Drive208-240/1/60 0140L00510 REV a INSTALLER/SERVICEMANCPG0360480901D Single Phase 240V/60HZ Direct Drive 208-240/1/60 0140L00506 REV a YL/PK CPG0060*1D Single Phase 240V/60HZ Direct Drive240/1/60 0140L00429 REV B IIC CPG060*3D Three Phase 208-230V/60HZ DirectIIC CPG060*3D Three Phase 208-230V/60HZ Direct DriveCPG036048*3D Three Phase 208-230V/60HZ Direct Drive 208-240/3/60 0140L00512 REV a CPG036048*3D Three Phase 230V/60HZ Direct Drive 208-240/3/60 0140L00507 REV a 460-575/3/60 0140L00870 REV a 460-575/3/60 0140L00870 REV a IIC 208-240/3/60 0140L00981 REV a GND Comp CPG0360480454B Three Phase 575V/60HZ Belt Drive460-575/3/60 0140L00871 REV a CPG0360480453B Three Phase 240V/60HZ Belt Drive 208-240/3/60 0140L00979 REV a Goodman Manufacturing Company, L.P
Related manuals
Manual 32 pages 5.71 Kb

CPG SERIES specifications

Goodman Manufacturing has long been a trusted name in the HVAC industry, known for delivering reliable and efficient heating and cooling solutions. Among its impressive lineup is the CPG series, a collection of packaged units that cater to a wide range of residential and commercial applications. The CPG series is designed with the latest technologies and features, making it an ideal choice for those seeking comfort and performance.

One of the most significant characteristics of the CPG series is its energy efficiency. Engineered to meet rigorous energy standards, these units utilize advanced refrigerant technologies that not only lower energy consumption but also contribute to reducing environmental impact. The high-efficiency scroll compressor within the CPG series is designed to operate quietly and smoothly, ensuring that homeowners enjoy a comfortable indoor environment without disruptive noise.

The CPG series also stands out with its robust construction. Each unit is crafted from durable materials that can withstand various weather conditions, ensuring longevity and reliability. The all-aluminum evaporator coil enhances corrosion resistance, prolonging the unit's lifespan and maintaining optimal performance throughout its operation.

In terms of features, the CPG series offers an integrated microprocessor control system that optimizes performance based on real-time environmental data. This smart technology allows for accurate temperature control and improved efficiency by adapting to changing conditions. Furthermore, the series provides multiple capacity options, making it flexible for various building sizes and requirements.

Ease of installation and maintenance is another hallmark of the CPG series. These packaged units are designed for quick setup, reducing labor costs and installation time. Additionally, the access panels on the units are strategically placed, facilitating easier maintenance and servicing. This advantage not only enhances user convenience but also ensures that the units operate efficiently for years to come.

Moreover, the CPG series supports various accessories and enhancements, such as advanced filtration systems and programmable thermostats, allowing users to customize their HVAC system based on specific needs and preferences.

In conclusion, the Goodman CPG series embodies a perfect blend of efficiency, durability, and technology. With its focus on energy savings and user-friendly design, it represents a sound investment for those seeking superior HVAC solutions for their homes or commercial spaces. Whether it's for new construction or an upgrade to an existing system, the CPG series offers performance and reliability that customers can depend on.