Goodman Mfg SS-CPC90-150 Model, KW Correction Factor for 1- & 3-Phase Units Supply Voltage

Page 11

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (A Modles)

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 208 / 240V

at 208 / 240V

at 240V

Airflow Range

 

 

 

 

 

CPC090XXX3BXXX

40

50

 

 

EHK3-16

48 / 55

50 / 60

15

3000 - 3375 CFM

EHK3-30

87 / 100

90 / 100

30

3000 - 3375 CFM

EHK3-45

121 / 139

125 / 150

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 480V

at 480V

at 480V

Airflow Range

 

 

 

 

 

CPC090XXX4BXXX

19

25

 

 

EHK4-16

27

30

15

3000 - 3375 CFM

EHK4-30

50

50

30

3000 - 3375 CFM

EHK4-45

70

70

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 575V

at 575V

at 575V

Airflow Range

 

 

 

 

 

CPC090XXX7BXXX

14

15

 

 

EHK7-16

22

25

15

---

EHK7-30

41

45

30

---

EHK7-45

57

60

43

---

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

² Maximum Overcurrent Protection device

KW Correction Factors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

 

220

210

208

 

 

 

 

 

 

 

Correction Factor

1

0.93

 

0.82

0.78

0.76

 

 

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 480V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

460

440

 

430

 

 

 

 

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

 

 

 

 

For other voltage, use voltage² / 480²

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 575V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW.

Minimum Airflow for Electric Heat

Heater Size (kW)

Minimum CFM

 

 

15

3,000

 

 

30

3,000

 

 

43

3,000

 

 

SS-CPC90-150

www.goodmanmfg.com

11

Image 11
Contents CPC Commercial Configuraon NomenclatureModels Electrical Data / Static CPC102Evapoartor Motor / Coil Rows Deep Fins per Inch CPC120Total BTU/h Sensible BTU/h Decibels ARI Reference #s 118,000Evapoartor Motor / Coil Operating Weight lbsShip Weight lbs Cooling CapacityHigh-Static Belt Drive Horizontal for a Models only Standard Belt Drive Down ShotHigh-Static Belt Drive Down Shot for a Models only Standard Belt Drive HorizontalHigh-Static Belt-Drive Horizontal Airflow Data 8½ TonsHigh-Static Belt-Drive Down Shot Standard Belt-Drive Horizontal Standard Belt-Drive Down ShotHigh-Static Belt Drive Airflow Data 12½ TonsKW Correction Factor for 575V Units Supply Voltage KW Correction Factor for 1- & 3-Phase Units Supply VoltageModel Correction FactorEHK3-16 3000 3375 CFM EHK3-30 100 EHK3-45 136 150 3400 3825 CFM Heat Kit Electrical Data Blower Only, Heat Mode 8½ TonsKW Correction Factor for 575V Units Heat Kit Electrical Data Blower Only, Heat Mode 10 TonsKW Correction Factor for 1- & 3-Phase Units Heat Kit Usage Airflow RangeEHK7-16 4000 EHK7-30 4300 EHK7-45 4500 Heat Kit Electrical Data Blower Only, Heat Mode 12½ Tons24.6 Airflow83.4 20.0Expanded Cooling Data 7½ Tons a Models 127 Ata 7½ Tons B Models81.5 25.1Expanded Cooling Data 7½ Tons B Models 383 Ata 8½ Tons94.5 Expanded Cooling Data 8½ Tons 131 Ata 10 Tons109.3 386144 Expanded Cooling Data 10 Tons118.0 412123 Ata 12½ Tons135.3 44.3136 Expanded Cooling Data 12½ Tons146.0 45.9Size Model DimensionsElectrical Entrance Locations Unit ClearancesCorner & Center-of-Gravity Locations Roof Curb Installation RiggingView Power death Product Specifications Wiring Diagram CPC090-150 Wiring Diagram CPC090-150 Item # Description Fits Model Sizes AccessoriesProduct Specifications Product Specifications