Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (A Modles)
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range |
|
|
|
|
|
CPC090XXX3BXXX | 40 | 50 |
|
|
48 / 55 | 50 / 60 | 15 | 3000 - 3375 CFM | |
87 / 100 | 90 / 100 | 30 | 3000 - 3375 CFM | |
121 / 139 | 125 / 150 | 43 | 3000 - 3375 CFM | |
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | at 480V | at 480V | at 480V | Airflow Range |
|
|
|
|
|
CPC090XXX4BXXX | 19 | 25 |
|
|
27 | 30 | 15 | 3000 - 3375 CFM | |
50 | 50 | 30 | 3000 - 3375 CFM | |
70 | 70 | 43 | 3000 - 3375 CFM | |
|
|
|
|
|
Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended |
Heat Kit Usage | at 575V | at 575V | at 575V | Airflow Range |
|
|
|
|
|
CPC090XXX7BXXX | 14 | 15 |
|
|
22 | 25 | 15 | ||
41 | 45 | 30 | ||
57 | 60 | 43 | ||
|
|
|
|
|
¹ Minimum Circuit Ampacity |
|
|
|
|
² Maximum Overcurrent Protection device
KW Correction Factors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage | 240 | 230 |
| 220 | 210 | 208 |
|
|
|
|
|
|
|
Correction Factor | 1 | 0.93 |
| 0.82 | 0.78 | 0.76 |
|
|
|
|
|
|
|
|
|
|
| |||
kW Correction Factor (for 480V Units) |
|
|
| |||
|
|
|
|
|
|
|
Supply Voltage | 460 | 440 |
| 430 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.92 | 0.84 |
| 0.8 |
|
|
|
|
|
|
|
|
|
For other voltage, use voltage² / 480² |
|
|
|
|
| |
|
|
|
| |||
kW Correction Factor (for 575V Units) |
|
|
| |||
|
|
|
|
|
|
|
Supply Voltage | 560 | 550 |
| 540 |
|
|
|
|
|
|
|
|
|
Correction Factor | 0.95 | 0.91 |
| 0.88 |
|
|
|
|
|
|
|
|
|
Multiply rated kW by correction factor to get actual kW.
Minimum Airflow for Electric Heat
Heater Size (kW) | Minimum CFM |
|
|
15 | 3,000 |
|
|
30 | 3,000 |
|
|
43 | 3,000 |
|
|
www.goodmanmfg.com | 11 |