Goodman Mfg SS-CPC90-150 dimensions Models

Page 3

Product Specifications

Product Specifications — 7½ Tons

 

A Models

 

B Models

 

 

 

 

 

 

 

 

 

 

 

CPC090

CPC090

CPC090

CPC090

CPC090

 

XXX3BXXX

XXX4BXXX

XXX3BXXX

XXX4BXXX

XXX7BXXX

 

 

 

 

 

 

Cooling Capacity

 

 

 

 

 

 

 

 

 

 

 

Total BTU/h

90,000

90,000

90,000

90,000

90,000

 

 

 

 

 

 

Sensible BTU/h

65,700

65,700

64,000

64,000

64,000

 

 

 

 

 

 

EER / IEER

11.5 / 11.5

11.5 / 11.5

11.5 / 11.5

11.5 / 11.5

11.5 / 11.5

Decibels

82.0

82.0

82.0

82.0

82.0

 

 

 

 

 

 

AHRI Reference #s

3000986

3000986

3620223

3620223

3620223

 

 

 

 

 

 

Evaporator Motor / Coil

 

 

 

 

 

 

 

 

 

 

 

Motor Type

Belt Drive

Belt Drive

Belt Drive

Belt Drive

Belt Drive

 

 

 

 

 

 

Indoor Nominal CFM

3,000

3,000

3,000

3,000

3,000

Indoor Motor FLA (Cooling)

7.8

3.9

5.0

2.5

2.3

 

 

 

 

 

 

Horsepower / RPM

2.0 / 1725

2.0 / 1725

1.5 / 1745

1.5 / 1745

1.5 / 1725

 

 

 

 

 

 

Piston Size (Cooling)

0.076

0.076

0.078

0.078

0.078

 

 

 

 

 

 

Filter Size (Qty)

(4) 16”x24”x2”

(4) 16”x24”x2”

(4) 16”x20”x2”

(4) 16”x20”x2”

(4) 16”x20”x2”

 

 

 

 

 

 

Drain Size (NPT)

¾”

¾”

¾”

¾”

¾”

R-410A Refrigerant Charge Cir #1 & #2

215 oz.

215 oz.

175 oz.

175 oz.

175 oz.

 

 

 

 

 

 

Evaporator Coil Face Area (ft²)

10.2

10.2

8.9

8.9

8.9

 

 

 

 

 

 

Rows Deep / Fins per Inch

4 / 16

4 / 16

4 / 16

4 / 16

4 / 16

 

 

 

 

 

 

Belt Drive Evap Fan Data

 

 

 

 

 

 

 

 

 

 

 

# of Wheels (D x W)

1 (15” x 12”)

1 (15” x 12”)

1 (15” x 12”)

1 (15” x 12”)

1 (15” x 12”)

Motor Sheave / Blower Sheave

VL40 / AK74

VL40 / AK74

VL40 / AK74

VL40 / AK74

VL40 / AK74

 

 

 

 

 

 

Belt

AX51

AX51

AX51

AX51

AX51

 

 

 

 

 

 

Condenser Fan / Coil

 

 

 

 

 

 

 

 

 

 

 

Quantity of Condenser Fan Motors

2

2

2

2

2

 

 

 

 

 

 

Horsepower - RPM

¼ - 1090

¼ - 890

¼ - 1075

¼ - 890

¼ - 1,075

Fan Diameter / # Fan Blades

22 / 4

22 / 4

22 / 4

22 / 4

22 / 4

 

 

 

 

 

 

Outdoor Nominal CFM

7,600

7,600

7,600

7,600

7,600

 

 

 

 

 

 

Face Area (ft²)

32.4

32.4

26.5

26.5

26.5

 

 

 

 

 

 

Rows Deep / Fins per Inch

2 / 20

2 / 20

2 / 22

2 / 22

2 / 22

 

 

 

 

 

 

Compressor

 

 

 

 

 

Quantity / Type

2 / Scroll

2 / Scroll

2 / Scroll

2 / Scroll

2 / Scroll

 

 

 

 

 

 

Stage

1

1

1

1

1

 

 

 

 

 

 

Electrical Data

 

 

 

 

 

 

 

 

 

 

 

Voltage-Phase-Frequency

208/230-3-60

460-3-60

208/230-3-60

460-3-60

575-3-60

 

 

 

 

 

 

Quantity of Compressors

2

2

2

2

2

Compressor RLA / LRA

13.1 / 83.1

6.1 / 41.0

13.1 / 83.1

6.1 / 41.0

4.4 / 33.0

 

 

 

 

 

 

Max External Static

1.5”

1.5”

1.0”

1.0”

1.0”

 

 

 

 

 

 

Outdoor Fan HP / RLA

(2) ¼ / 1.4

(2) ¼ / 0.8

(2) ¼ / 1.4

(2) ¼ / 0.8

(2) ¼ / 0.6

 

 

 

 

 

 

Total Unit Amps

36.9

17.7

34.0

16.3

12.3

 

 

 

 

 

 

Min. Circuit Ampacity¹

40

19

37.3

17.8

13.4

Max. Overcurrent Protection (amps)²

50

25

50

20

15

 

 

 

 

 

 

Entrance Power Supply

Locating

Locating

Locating

Locating

Locating

Entrance Control Voltage

Dimple

Dimple

Dimple

Dimple

Dimple

 

 

 

 

 

 

Operating Weight (lbs)

1110

1110

975

975

975

 

 

 

 

 

 

Ship Weight (lbs)

1150

1150

1000

1000

1000

¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

SS-CPC90-150

www.goodmanmfg.com

3

Image 3
Contents CPC Commercial Configuraon NomenclatureModels CPC102 Evapoartor Motor / CoilElectrical Data / Static Rows Deep Fins per Inch CPC120Total BTU/h Sensible BTU/h Decibels ARI Reference #s 118,000Evapoartor Motor / Coil Operating Weight lbsShip Weight lbs Cooling CapacityHigh-Static Belt Drive Horizontal for a Models only Standard Belt Drive Down ShotHigh-Static Belt Drive Down Shot for a Models only Standard Belt Drive HorizontalAirflow Data 8½ Tons High-Static Belt-Drive Down ShotHigh-Static Belt-Drive Horizontal Standard Belt-Drive Horizontal Standard Belt-Drive Down ShotHigh-Static Belt Drive Airflow Data 12½ TonsKW Correction Factor for 575V Units Supply Voltage KW Correction Factor for 1- & 3-Phase Units Supply VoltageModel Correction FactorEHK3-16 3000 3375 CFM EHK3-30 100 EHK3-45 136 150 3400 3825 CFM Heat Kit Electrical Data Blower Only, Heat Mode 8½ TonsKW Correction Factor for 575V Units Heat Kit Electrical Data Blower Only, Heat Mode 10 TonsKW Correction Factor for 1- & 3-Phase Units Heat Kit Usage Airflow RangeEHK7-16 4000 EHK7-30 4300 EHK7-45 4500 Heat Kit Electrical Data Blower Only, Heat Mode 12½ Tons24.6 Airflow83.4 20.0Expanded Cooling Data 7½ Tons a Models 127 Ata 7½ Tons B Models81.5 25.1Expanded Cooling Data 7½ Tons B Models Ata 8½ Tons 94.5383 Expanded Cooling Data 8½ Tons 131 Ata 10 Tons109.3 386144 Expanded Cooling Data 10 Tons118.0 412123 Ata 12½ Tons135.3 44.3136 Expanded Cooling Data 12½ Tons146.0 45.9Size Model DimensionsElectrical Entrance Locations Unit ClearancesCorner & Center-of-Gravity Locations Roof Curb Installation RiggingView Power death Product Specifications Wiring Diagram CPC090-150 Wiring Diagram CPC090-150 Item # Description Fits Model Sizes AccessoriesProduct Specifications Product Specifications