Product Specifications
Product Specifications — 8½ Tons
CPC102
XXX3BXXX
CPC102
XXX4BXXX
CPC102
XXX7BXXX
Cooling Capacity
Total, BTU/h
Sensible BTU/h
EER / IEER
Decibels
ARI Reference #s
102,000 | 102,000 | 102,000 |
70,380 | 70,380 | 70,380 |
11.3 / 11.2 | 11.3 / 11.2 | 11.3 / 11.2 |
83 | 83 | 83 |
3620220 | 3620220 | 3620220 |
|
|
|
Evapoartor Motor / Coil
Motor Type | Belt Drive | Belt Drive | Belt Drive |
|
|
|
|
Indoor Nominal CFM | 3,400 | 3,400 | 3,400 |
|
|
|
|
Indoor Motor FLA (Cooling) | 7.8 | 3.9 | 2.3 |
|
|
|
|
Horsepower - RPM | 1725 | 1725 | 1725 |
|
|
|
|
Piston Size (Cooling) | 0.08 | 0.08 | 0.08 |
|
|
|
|
Filter Size (Qty) | (4) 16” x 20” x 2” | (4) 16” x 20” x 2” | (4) 16” x 20” x 2” |
|
|
|
|
Drain Size (NPT) | 3/4" | 3/4" | 3/4" |
|
|
|
|
180 oz. | 180 oz. | 180 oz. | |
|
|
|
|
Evaporator Coil Face Area (ft2) | 8.9 | 8.9 | 8.9 |
|
|
|
|
Rows Deep / Fins per Inch | 4 / 16 | 4 / 16 | 4 / 16 |
|
|
|
|
Belt Drive Evap Fan Data |
|
|
|
|
|
|
|
# of Wheels (D x W) | 1 (15" x 12") | 1 (15" x 12") | 1 (15" x 12") |
|
|
|
|
Motor Sheave / Blower Sheave | VL40 / AK74 | VL40 / AK74 | VL40 / AK74 |
|
|
|
|
Belt | AX51 | AX51 | AX51 |
|
|
|
|
Condenser Fan / Coil |
|
|
|
|
|
|
|
Quantity of Condenser Fan Motors | 2 | 2 | 2 |
|
|
|
|
Horsepower - RPM | 1/4" - 1,090 | 1/4" - 890 | 1/4" - 1,075 |
|
|
|
|
Fan Diameter / # Fan Blades | 22 / 4 | 22 / 4 | 22 / 4 |
|
|
|
|
Outdoor Nominal CFM | 7,600 | 7,600 | 7,600 |
|
|
|
|
Face Area (ft2) | 13.25 | 13.25 | 13.25 |
|
|
|
|
Rows Deep / Fins per Inch | 2 / 22 | 2 / 22 | 2 / 22 |
|
|
|
|
Compressor |
|
|
|
Quantity / Type
Stage
2 / Scroll | 2 / Scroll | 2 / Scroll |
1 | 1 | 1 |
|
|
|
Electrical Data / Static
Voltage / Phase / Frequency | 230 / 3 / 60 | 460 / 3 / 60 | 575 / 3 / 60 |
|
|
|
|
Quantity of Compressors | 2 | 2 | 2 |
|
|
|
|
Compressor RLA / LRA ea. | 14.5 / 98 | 6.3 / 55 | 6.0 / 41 |
|
|
|
|
Standard Max Static | 1" | 1 | 1 |
|
|
|
|
Outdoor Fan FLA ea. | 1.4 | 0.8 | 0.6 |
|
|
|
|
Total Unit Amps | 39.6 | 18.1 | 15.5 |
|
|
|
|
Min. Circuit Ampacity¹ | 43.2 | 19.7 | 17 |
|
|
|
|
Max. Overcurrent Protection (amps)² | 50 | 25 | 20 |
|
|
|
|
Entrance Power Supply | Locating | Locating | Locating |
Entrance Control Voltage | Dimple | Dimple | Dimple |
|
|
|
|
Operating Weight (lbs) | 975 | 975 | 975 |
|
|
|
|
Ship Weight (lbs) | 1000 | 1000 | 1000 |
|
|
|
|
¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or
Note: Always check the S&R plate for electrical data on the unit being installed.
4 | www.goodmanmfg.com |