Goodman Mfg SS-CPC90-150 dimensions EHK3-16 3000 3375 CFM EHK3-30 100 EHK3-45 136 150

Page 12

Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (B Modles)

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 240V

at 240V

at 240V

Airflow Range

 

 

 

 

 

CPC090XXX3BXXX

37

50

 

 

EHK3-16

51

60

15

3000 - 3375 CFM

EHK3-30

97

100

30

3000 - 3375 CFM

EHK3-45

136

150

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 480V

at 480V

at 480V

Airflow Range

 

 

 

 

 

CPC090XXX4BXXX

18

20

 

 

EHK4-16

26

30

15

3000 - 3375 CFM

EHK4-30

48

50

30

3000 - 3375 CFM

EHK4-45

68

70

43

3000 - 3375 CFM

 

 

 

 

 

Model and

MCA¹

MOP² (amps)

Actual kW

Recommended

Heat Kit Usage

at 575V

at 575V

at 575V

Airflow Range

 

 

 

 

 

CPC090XXX7BXXX

13

15

 

 

EHK7-16

22

25

15

3000 - 3375 CFM

EHK7-30

41

45

30

3000 - 3375 CFM

EHK7-45

57

60

43

3000 - 3375 CFM

 

 

 

 

 

¹ Minimum Circuit Ampacity

 

 

 

 

² Maximum Overcurrent Protection device

KW Correction Factors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

 

220

210

208

 

 

 

 

 

 

 

Correction Factor

1

0.93

 

0.82

0.78

0.76

 

 

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 480V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

460

440

 

430

 

 

 

 

 

 

 

 

 

Correction Factor

0.92

0.84

 

0.8

 

 

 

 

 

 

 

 

 

For other voltage, use voltage² / 480²

 

 

 

 

 

 

 

 

 

kW Correction Factor (for 575V Units)

 

 

 

 

 

 

 

 

 

 

Supply Voltage

560

550

 

540

 

 

 

 

 

 

 

 

 

Correction Factor

0.95

0.91

 

0.88

 

 

 

 

 

 

 

 

 

Multiply rated kW by correction factor to get actual kW.

Minimum Airflow for Electric Heat

Heater Size (kW)

Minimum CFM

 

 

15

3,000

 

 

30

3,000

 

 

43

3,000

 

 

12

www.goodmanmfg.com

SS-CPC90-150

Image 12
Contents CPC Commercial Nomenclature ConfiguraonModels CPC102 Evapoartor Motor / CoilElectrical Data / Static CPC120 Total BTU/h Sensible BTU/hDecibels ARI Reference #s 118,000 Rows Deep Fins per InchOperating Weight lbs Ship Weight lbsCooling Capacity Evapoartor Motor / CoilStandard Belt Drive Down Shot High-Static Belt Drive Down Shot for a Models onlyStandard Belt Drive Horizontal High-Static Belt Drive Horizontal for a Models onlyAirflow Data 8½ Tons High-Static Belt-Drive Down ShotHigh-Static Belt-Drive Horizontal Standard Belt-Drive Down Shot Standard Belt-Drive HorizontalAirflow Data 12½ Tons High-Static Belt DriveKW Correction Factor for 1- & 3-Phase Units Supply Voltage ModelCorrection Factor KW Correction Factor for 575V Units Supply VoltageEHK3-16 3000 3375 CFM EHK3-30 100 EHK3-45 136 150 Heat Kit Electrical Data Blower Only, Heat Mode 8½ Tons 3400 3825 CFMHeat Kit Electrical Data Blower Only, Heat Mode 10 Tons KW Correction Factor for 1- & 3-Phase UnitsHeat Kit Usage Airflow Range KW Correction Factor for 575V UnitsHeat Kit Electrical Data Blower Only, Heat Mode 12½ Tons EHK7-16 4000 EHK7-30 4300 EHK7-45 4500Airflow 83.420.0 24.6Expanded Cooling Data 7½ Tons a Models Ata 7½ Tons B Models 81.525.1 127Expanded Cooling Data 7½ Tons B Models Ata 8½ Tons 94.5383 Expanded Cooling Data 8½ Tons Ata 10 Tons 109.3386 131Expanded Cooling Data 10 Tons 118.0412 144Ata 12½ Tons 135.344.3 123Expanded Cooling Data 12½ Tons 146.045.9 136Model Dimensions SizeUnit Clearances Electrical Entrance LocationsRoof Curb Installation Rigging Corner & Center-of-Gravity LocationsView Power death Product Specifications Wiring Diagram CPC090-150 Wiring Diagram CPC090-150 Accessories Item # Description Fits Model SizesProduct Specifications Product Specifications