Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) — 10 Tons
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC120XXX3BXXX | 49 | 60 | 
 | 
 | 
| 48 / 55 | 50 / 60 | 15 | 3500 - 4500 CFM | |
| 87 / 100 | 90 / 100 | 30 | 3500 - 4500 CFM | |
| 121 / 139 | 125 / 150 | 43 | 4000 - 4500 CFM | 
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 208 / 240V | at 208 / 240V | at 240V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC120XXX3HXXX | 50 | 60 | 
 | 
 | 
| 49 / 57 | 50 / 60 | 15 | 3500 - 4500 CFM | |
| 88 / 102 | 90 / 110 | 30 | 3500 - 4500 CFM | |
| 122 / 141 | 125 / 150 | 43 | 4000 - 4500 CFM | 
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 480V | at 480V | at 480V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC120XXX4BXXX | 24 | 30 | 
 | 
 | 
| 27 | 30 | 15 | 3500 - 4500 CFM | |
| 50 | 50 | 30 | 3500 - 4500 CFM | |
| 70 | 70 | 43 | 4000 - 4500 CFM | |
| 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
| Model and | MCA¹ | MOP² (amps) | Actual kW | Recommended | 
| Heat Kit Usage | at 575V | at 575V | at 575V | Airflow Range | 
| 
 | 
 | 
 | 
 | 
 | 
| CPC0120XXX7BXXX | 17 | 20 | 
 | 
 | 
| 22 | 25 | 15 | 3500 - 4500 CFM | |
| 41 | 45 | 30 | 3500 - 4500 CFM | |
| 57 | 60 | 43 | 4000 - 4500 CFM | |
| 
 | 
 | 
 | 
 | 
 | 
| ¹ Minimum Circuit Ampacity | 
 | 
 | 
 | 
 | 
² Maximum Overcurrent Protection device
kW Correction Factor
kW Correction Factor (for 1- & 3-Phase  Units)
| Supply Voltage | 240 | 230 | 220 | 210 | 208 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 1 | 0.93 | 0.82 | 0.78 | 0.76 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
| kW Correction Factor for 480V Units | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
| Actual Voltage | 460 | 440 | 
 | 430 | 
| 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 0.92 | 0.84 | 
 | 0.8 | 
| 
 | 
 | 
 | 
 | 
 | 
| For other voltage use voltage² / 480² | 
 | 
 | 
 | |
| 
 | 
 | |||
| kW Correction Factor for 575V Units | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
| Supply Voltage | 560 | 550 | 
 | 540 | 
| 
 | 
 | 
 | 
 | 
 | 
| Correction Factor | 0.95 | 0.91 | 
 | 0.88 | 
| 
 | 
 | 
 | 
 | 
 | 
Multiply rated kW by correction factor to get actual kW
Minimum Airflow for Electric Heat
| Heater Size (kW) | Min. CFM | Min. CFM | |
| 
 | Horizontal | ||
| 
 | |||
| 
 | 
 | 
 | |
| 15 | 4,000 | 4,000 | |
| 
 | 
 | 
 | |
| 30 | 4,000 | 4,000 | |
| 
 | 
 | 
 | |
| 43 | 4,000 | 4,000 | |
| 
 | 
 | 
 | 
| 14 | www.goodmanmfg.com |