Goodman Mfg SS-CPC90-150 CPC120, Total BTU/h Sensible BTU/h, Decibels ARI Reference #s 118,000

Page 5

Product Specifications

Product Specifications — 10 Tons

CPC120

XXX3BXXX

CPC120

XXX4BXXX

CPC120

XXX7BXXX

Cooling Capacity

Total BTU/h

Sensible BTU/h

EER / IEER

Decibels

ARI Reference #s

118,000

118,000

118,000

87,300

87,300

87,300

11.5 / 11.2

11.5 / 11.2

11.5 / 11.2

83.0

83.0

83.0

3023833

3023833

3023833

 

 

 

Evaporator Motor / Coil

Motor Type

Belt Drive

Belt Drive

Belt Drive

 

 

 

 

Indoor Nominal CFM

4,000

4,000

4,000

 

 

 

 

Indoor motor FLA (Cooling)

7.8

3.9

2.7

 

 

 

 

Horsepower - RPM

2.0/1725

2.0/1725

2.0/1725

 

 

 

 

Piston Size (Cooling)

0.086

0.086

0.086

 

 

 

 

Filter Size (Qty)

(4) 16” x 24” x 2”

(4) 16” x 24” x 2”

(4) 16” x 24” x 2”

 

 

 

 

Drain Size (NPT)

¾”

¾”

¾”

 

 

 

 

R-410A Refrigerant Charge Cir #1 & #2

220 oz.

220 oz.

220 oz.

 

 

 

 

Evaporator Coil Face Area (ft²)

10.2

10.2

10.2

 

 

 

 

Rows Deep / Fins per Inch

4 / 14

4 / 14

4 / 14

 

 

 

 

Belt Drive Evap Fan Data

 

 

 

 

 

 

 

# of Wheels (D x W)

(1) 15” x 15”

(1) 15” x 15”

(1) 15” x 15”

 

 

 

 

Motor Sheave / Blower Sheave

VL40 / AK74

VL40 / AK74

VL40 / AK74

 

 

 

 

Belt

AX51

AX51

AX51

 

 

 

 

Condenser Fan / Coil

 

 

 

 

 

 

 

Quantity of Condenser Fan Motors

2

2

2

 

 

 

 

Horsepower - RPM

⅓ - 1,075

⅓ - 1,075

⅓ - 1,075

 

 

 

 

Fan Diameter / # Fan Blades

22 / 3

22 / 3

22 / 3

 

 

 

 

Outdoor Nominal CFM

7,200

7,200

7,200

 

 

 

 

Face Area (ft²)

32.4

32.4

32.4

 

 

 

 

Rows Deep - Fins per Inch

2/2 rows - 22 fpi

2/2 rows - 22 fpi

2/2 rows - 22 fpi

 

 

 

 

Compressor

 

 

 

 

 

 

 

Quantity / Type

Stage

Electrical Data

2 / Scroll

2 / Scroll

2 / Scroll

1

1

1

Voltage/Phase/ Frequency

208-230/3/60

460/3/60

575/3/60

 

 

 

 

Quantity of Compressors

2

2

2

 

 

 

 

Compressor RLA / LRA ea.

16/110.0

7.8/52.0

5.7/38.9

 

 

 

 

Standard Max Static

2.0”

2.0”

2.0”

 

 

 

 

Outdoor Fan RLA ea.

2.40

1.20

0.89

 

 

 

 

Total Unit Amps

45

22

16

 

 

 

 

Min. Circuit Ampacity¹

49

24

17

 

 

 

 

Max. Overcurrent Protection (amps)²

60.0

30

20

 

 

 

 

Entrance Power Supply

Locating

Locating

Locating

Entrance Control Voltage

Dimple

Dimple

Dimple

 

 

 

 

Operating Weight (lbs)

1135

1135

1135

 

 

 

 

Ship Weight (lbs)

1175

1175

1175

 

 

 

 

¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

SS-CPC90-150

www.goodmanmfg.com

5

Image 5
Contents CPC Commercial Configuraon NomenclatureModels Electrical Data / Static CPC102Evapoartor Motor / Coil Total BTU/h Sensible BTU/h CPC120Decibels ARI Reference #s 118,000 Rows Deep Fins per InchShip Weight lbs Operating Weight lbsCooling Capacity Evapoartor Motor / CoilHigh-Static Belt Drive Down Shot for a Models only Standard Belt Drive Down ShotStandard Belt Drive Horizontal High-Static Belt Drive Horizontal for a Models onlyHigh-Static Belt-Drive Horizontal Airflow Data 8½ TonsHigh-Static Belt-Drive Down Shot Standard Belt-Drive Horizontal Standard Belt-Drive Down ShotHigh-Static Belt Drive Airflow Data 12½ TonsModel KW Correction Factor for 1- & 3-Phase Units Supply VoltageCorrection Factor KW Correction Factor for 575V Units Supply VoltageEHK3-16 3000 3375 CFM EHK3-30 100 EHK3-45 136 150 3400 3825 CFM Heat Kit Electrical Data Blower Only, Heat Mode 8½ TonsKW Correction Factor for 1- & 3-Phase Units Heat Kit Electrical Data Blower Only, Heat Mode 10 TonsHeat Kit Usage Airflow Range KW Correction Factor for 575V UnitsEHK7-16 4000 EHK7-30 4300 EHK7-45 4500 Heat Kit Electrical Data Blower Only, Heat Mode 12½ Tons83.4 Airflow20.0 24.6Expanded Cooling Data 7½ Tons a Models 81.5 Ata 7½ Tons B Models25.1 127Expanded Cooling Data 7½ Tons B Models 383 Ata 8½ Tons94.5 Expanded Cooling Data 8½ Tons 109.3 Ata 10 Tons386 131118.0 Expanded Cooling Data 10 Tons412 144135.3 Ata 12½ Tons44.3 123146.0 Expanded Cooling Data 12½ Tons45.9 136Size Model DimensionsElectrical Entrance Locations Unit ClearancesCorner & Center-of-Gravity Locations Roof Curb Installation RiggingView Power death Product Specifications Wiring Diagram CPC090-150 Wiring Diagram CPC090-150 Item # Description Fits Model Sizes AccessoriesProduct Specifications Product Specifications