Friedrich Complete Thermostat Manual for Efficient Control of Air Conditioner Units

Page 13

Low Voltage Interface Connections

All Vert-I-Pak units have a low voltage interface connector through which a Remote Wall Thermostat, Desk Control and Auxiliary Fan’s Relay can be connected. The interface connector is located on the electronic control board.

Figure 1 Interface Connector Location

Questions concerning proper connections to the unit should be dirrected to the factory.

Table 1

 

Interface Connector Definitions

FP

Factory use only.

 

(Ensure there is no jumper at FP an F2)

F2

Used with F1 to provide 24 VAC to external

fan relay. (Ensure there is no jumper at FP an F2)

 

F1

Used with F2 to provide 24 VAC to

external fan relay.

 

D2

Used with D1 for desk control on or off

operation.

 

 

D1

Used with D2 for desk control on or off

operation.

CCommon Ground Terminal

GH

Call for high fan

 

 

GL

Call for low fan

BCall for heat pump reversing valve Y Call for compressor

W Call for heating

R 24V Power from Electronic Control to Wall

Remote Wall Thermostat

All Friedrich Vert-I-Pak units are factory configured to be controlled by using a single stage heat/cool remote wired wall mounted thermostat.

Thermostat Selection

Friedrich recommends the use of the Friedrich RT4 and RT6. These thermostats are single stage heat/cool, manual changeover. The RT4 is a digital display thermostat with single speed fan control. The RT6 features a digital display, two fan speed selection, temperature limiting, status indicator light, room temperature offset, and backlight. Other thermostats may be used as long as they are single stage heat/cool and are configured correctly for the unit.

Thermostat terminals requirements:.

For cooling with electric heat units: C, R, G, Y, W.

For heat pump units: C, R, G, Y, W, B.

For two fan speeds, thermostat must have 2 fan speed selection.

HEAT PUMP UNITS

During Heat Mode:

The B terminal must be continuously energized. The W terminal must have 24 VAC output to call for heat. The control board decides on whether to turn on the Heat Pump Heat (compressor) or Electric Heat. The Y terminal should not have 24 VAC output during heat mode.

Connecting a Remote Wall Thermostat

WARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

Connect the thermostat using Figure 1 and Table 1 as a guide.

Procedure (Ensure there is no jumper wire at FP and F2)

1)Disconnect power to the unit.

2)Unscrew and remove the electrical control box’s cover.

3)Locate the Interface Connector (24 VAC terminal strip (See figure 1 at left).

4)Make the wire connections according to the configuration needed for

your unit (see above or page 40 for wiring diagrams). Use #18 gauge wire size.

5)Once each wire is matched and connected, the unit is now ready to be controlled by the thermostat.

6)Reattach the electrical control box’s cover.

12

Image 13
Contents Single Package Vertical Air Conditioning System Table of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionSerial Number 00001Year Manufactured Production RUN Number Product LineElectrical Requirements Chassis Specifi cations Cooling Performance Data Technical Service Data Quiet Start/Stop Electronic Control Board FeaturesHeat Mode in Cool with Electric Heat Units Compressor Lock Out Time Electric Shock Hazard Low Voltage Interface ConnectionsCUT/SEVER Hazard ServiceGround Air Intake Vpak 9-18K BTU Units Components IdentificationAir Intake Front Side Vpak 24K BTU Units Components IdentificationError Codes and Alarm Status Components Testing Fuse 10 Amps 250 VaC Capacitor Connections Capacitor Check with Capacitor AnalyzerBlower / FAN Motor Blower / FAN Motor TestDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsExternal Static Pressure Explanation of charts Refrigeration Sequence of Operation Refrigeration AssemblyEquipment Required Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockUndercharged Refrigerant Systems Method Of Charging / RepairsBurn Hazard Freeze HazardRestricted Refrigerant System Overcharged Refrigerant SystemsHeating Mode Cooling ModeHermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Single Phase Running and L.R.A. Test Single Phase ConnectionsLocked Rotor Voltage L.R.V. Test Determine L.R.VExternal Overload Vpak 9, 12, 18 K Btus Single Phase Resistance TestInternal Overload Vpak 24 K Btus Ground TestHigh Temperatures Recommended procedure for compressor replacementElectrical Shock Hazard Routine MaintenanceRoom AIR Conditioner Unit Performance Test Data Sheet THERMISTORS’ Resistance Values 9K BTU, 12K BTU, & 18K BTU Electrical Troubleshooting Chart CoolingCompressor outdoor Electrical Troubleshooting Chart Cooling 24K BTUHeat Pump Mode Electrical Troubleshooting Chart Heat PumpTroubleshooting Chart Heating Heat Pump Troubleshooting Chart CoolingHeat Pump with Electric Heat Remote Wall Thermostat Wiring DiagramsGH GL B Y RT6 6TR Cool with Electric HeatGH GL B Y W R GH GL O/B Y W Wiring Diagram Heat Pump EH 5KW, 10.0KW Model Description Photo Friedrich Air Conditioning Company Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models 9K-18K BTU/h Models Vpak Parts List Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models 24K BTU/h Models Vpak Parts List Technical Support Contact Information Friedrich AIR Conditioning CO