Friedrich R410A manual Overcharged Refrigerant Systems, Restricted Refrigerant System

Page 27

After the unit has run 10 to 15 minutes, check the gauge pressures.Gaugesconnectedtosystemwithanundercharge will have low head pressures and substantially low suction pressures.

Improper air fl ow over the evaporator coil may indicate some of the same symptoms as an over charged system. An overcharge can cause the compressor to fail, since it would be “slugged” with liquid refrigerant.

The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the air quantity over the evaporator coil is correct. Icing of the evaporator will not be encountered because the refrigerant will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of over charge). Suction pressure should be slightly higher.

Overcharged Refrigerant Systems

Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confi rm, remove some of the charge, if conditions improve, system may be overcharged. If conditions don’t improve, Noncondensables are indicated.

Wheneveranoverchargedsystemisindicated,alwaysmake sure that the problem is not caused by air fl ow problems.

Restricted Refrigerant System

Troubleshooting a restricted refrigerant system can be diffi cult. The following procedures are the more common problems and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.

A partial restriction allows some of the refrigerant to circulate through the system.

With a complete restriction there is no circulation of refrigerant in the system.

Restricted refrigerant systems display the same symptoms as a “low-charge condition.”

When the unit is shut off, the gauges may equalize very slowly.

Gauges connected to a completely restricted system will run in a deep vacuum. When the unit is shut off, the gauges

will not equalize at all.

A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.

Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction to the other.

With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor with a partial restriction may show normal current when compared to the unit specifi cation.

With a complete restriction the current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.

The following conditions are based primarily on a system in the cooling mode.

26

Image 27
Contents Single Package Vertical Air Conditioning System Table of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards IntroductionProduct Line 00001Serial Number Year Manufactured Production RUN NumberElectrical Requirements Chassis Specifi cations Cooling Performance Data Technical Service DataQuiet Start/Stop Electronic Control Board FeaturesHeat Mode in Cool with Electric Heat Units Compressor Lock Out Time Electric Shock Hazard Low Voltage Interface ConnectionsCUT/SEVER Hazard ServiceGround Air Intake Vpak 9-18K BTU Units Components IdentificationAir Intake Front Side Vpak 24K BTU Units Components IdentificationError Codes and Alarm Status Components Testing Fuse 10 Amps 250 VaC Blower / FAN Motor Test Capacitor Check with Capacitor AnalyzerCapacitor Connections Blower / FAN MotorDrain PAN Valve Heater Elements and Limit SWITCHES’ SpecificationsExternal Static Pressure Explanation of charts Refrigeration Sequence of Operation Refrigeration AssemblyRisk of Electric Shock Sealed Refrigeration System RepairsEquipment Required Equipment Must be CapableFreeze Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Burn HazardRestricted Refrigerant System Overcharged Refrigerant SystemsCapillary Tube Systems Cooling ModeHeating Mode Hermetic Components CheckReversing Valve DESCRIPTION/OPERATION Procedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleFire Hazard Determine L.R.V Single Phase ConnectionsSingle Phase Running and L.R.A. Test Locked Rotor Voltage L.R.V. TestGround Test Single Phase Resistance TestExternal Overload Vpak 9, 12, 18 K Btus Internal Overload Vpak 24 K BtusHigh Temperatures Recommended procedure for compressor replacementElectrical Shock Hazard Routine MaintenanceRoom AIR Conditioner Unit Performance Test Data Sheet THERMISTORS’ Resistance Values 9K BTU, 12K BTU, & 18K BTU Electrical Troubleshooting Chart CoolingCompressor outdoor Electrical Troubleshooting Chart Cooling 24K BTUHeat Pump Mode Electrical Troubleshooting Chart Heat PumpTroubleshooting Chart Heating Heat Pump Troubleshooting Chart CoolingHeat Pump with Electric Heat Remote Wall Thermostat Wiring DiagramsGH GL B Y RT6 6TR Cool with Electric HeatGH GL B Y W R GH GL O/B Y W Wiring Diagram Heat Pump EH 5KW, 10.0KW Model Description Photo Friedrich Air Conditioning Company Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models 9K-18K BTU/h Models Vpak Parts List Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models 24K BTU/h Models Vpak Parts List Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 45 pages 45.67 Kb Manual 7 pages 15.54 Kb Manual 27 pages 24.75 Kb