Friedrich R410A manual External Static Pressure

Page 22

External Static Pressure

External Static Pressure can best be defined as the pressure difference (drop) between the Positive Pressure (discharge) and the Negative Pressure (intake) sides of the blower. External Static Pressure is developed by the blower as a result of resistance to airflow (Friction) in the air distribution system EXTERNAL to the VERT-I-PAK cabinet.

Resistance applied externally to the VERT-I-PAK (i.e. duct work, filters, etc.) on either the supply or return side of the system causes an INCREASE in External Static Pres- sure accompanied by a REDUCTION in airflow.

External Static Pressure is affected by two (2) factors.

1.Resistance to Airflow as already explained.

2.Blower Speed. Changing to a higher or lower blower speed will raise or lower the External Static Pressure accordingly.

Theseaffectsmustbeunderstoodandtakenintoconsideration when checking External Static Pressure/Airflow to insure that the system is operating within design conditions.

Operating a system with insufficient or excessive airflow can cause a variety of different operating problems. Among these are reduced capacity, freezing evaporator coils, premature compressor and/or heating component failures. etc.

System airflow should always be verified upon completion of a new installation, or before a change-out, compressor replacement, or in the case of heat strip failure to insure that the failure was not caused by improper airflow.

1.Set up to measure external static pressure at the supply and return air.

2.Ensure the coil and filter are clean, and that all the registers are open.

3.Determine the external static pressure with the blower operating.

4.Refer to the Air Flow Data for your VERT-I-PAK system to find the actual airflow for factory-selected fan speeds.

5.If the actual airflow is either too high or too low, the blower speed will need to be changed to appropriate setting or the ductwork will need to be reassessed and corrections made as required.

6.Select a speed, which most closely provides the required airflow for the system.

7.Recheck the external static pressure with the new speed. External static pressure (and actual airflow) will have changed to a higher or lower value depending upon speed selected. Recheck the actual airflow (at this "new" static pressure) to confirm speed selection.

8.Repeat steps 8 and 9 (if necessary) until proper airflow has been obtained.

EXAMPLE: Airflow requirements are calculated as follows: (Having a wet coil creates additional resistance to airflow. This addit ional resistance must be taken into consideration to obtain accurate airflow information.

Checking External Static Pressure

The airflow through the unit can be determined by measuring the external static pressure of the system, and consulting the blower performance data for the specific VERT-I-PAK.

Determining the Indoor CFM: Chart A – CFM

 

 

 

MODEL

 

 

 

 

 

 

 

 

 

 

VEA09/VHA09

VEA12/VHA12

VEA18/VHA18

ESP (")

Low

High

Low

High

Low

High

.00"

340

385

420

470

430

480

.10"

300

340

350 *

420 **

400

450

.20"

230

280

290

350

340

400

.30”

140

190

250

300

290

330

Highlighted values indicate rated performance point. Rated performance for

*VEA12

Rated Performance for

**VHA12

 

 

Model

 

VEA24/VHA24

ESP (")

Low

 

High

.00"

690

 

740

.10"

610

 

700

.20"

560

 

640

.30"

510

 

580

.40"

450

 

520

Highlighted values indicate rated performance point.

21

Image 22
Contents Single Package Vertical Air Conditioning System Table of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage HazardsYear Manufactured Production RUN Number 00001Serial Number Product LineElectrical Requirements Chassis Specifi cations Technical Service Data Cooling Performance DataElectronic Control Board Features Quiet Start/StopHeat Mode in Cool with Electric Heat Units Compressor Lock Out Time Low Voltage Interface Connections Electric Shock HazardService CUT/SEVER HazardVpak 9-18K BTU Units Components Identification Ground Air IntakeVpak 24K BTU Units Components Identification Air Intake Front SideError Codes and Alarm Status Components Testing Fuse 10 Amps 250 VaC Blower / FAN Motor Capacitor Check with Capacitor AnalyzerCapacitor Connections Blower / FAN Motor TestHeater Elements and Limit SWITCHES’ Specifications Drain PAN ValveExternal Static Pressure Explanation of charts Refrigeration Assembly Refrigeration Sequence of OperationEquipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemHermetic Components Check Cooling ModeHeating Mode Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Locked Rotor Voltage L.R.V. Test Single Phase ConnectionsSingle Phase Running and L.R.A. Test Determine L.R.VInternal Overload Vpak 24 K Btus Single Phase Resistance TestExternal Overload Vpak 9, 12, 18 K Btus Ground TestRecommended procedure for compressor replacement High TemperaturesRoutine Maintenance Electrical Shock HazardRoom AIR Conditioner Unit Performance Test Data Sheet THERMISTORS’ Resistance Values Electrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Compressor outdoorElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpRemote Wall Thermostat Wiring Diagrams Heat Pump with Electric HeatGH GL B Y RT6 Cool with Electric Heat 6TRGH GL B Y W R GH GL O/B Y W Wiring Diagram Heat Pump EH 5KW, 10.0KW Model Description Photo Friedrich Air Conditioning Company Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models 9K-18K BTU/h Models Vpak Parts List Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models 24K BTU/h Models Vpak Parts List Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 45 pages 45.67 Kb Manual 7 pages 15.54 Kb Manual 27 pages 24.75 Kb

R410A specifications

Friedrich R410A is a refrigerant blend that has become a cornerstone in the HVAC industry, particularly for air conditioning systems. This hydrofluorocarbon (HFC) is known for its efficiency and environmentally friendly properties, making it a popular alternative to older refrigerants like R22.

One of the main features of R410A is its exceptional thermal efficiency. It has a higher cooling capacity compared to R22, which allows for smaller and more efficient equipment. This efficiency translates to reduced energy consumption and lower operating costs for users. Additionally, the higher pressure capability of R410A enables the design of more compact systems, which is particularly beneficial for residential and commercial applications where space is often limited.

R410A is characterized by its zero ozone depletion potential (ODP), which is a significant advantage over its predecessors. This makes it a more environmentally responsible choice, aligning with global initiatives to phase out substances that harm the ozone layer. However, it is essential to note that while R410A does not deplete the ozone, it does have a global warming potential (GWP) of approximately 2,088, making it less favorable in terms of climate impact compared to natural refrigerants.

In terms of technology, R410A is typically utilized in systems that are designed specifically for this refrigerant. Equipment compatible with R410A often features advanced components that can handle the higher pressures required. Many modern air conditioning systems equipped with R410A also incorporate variable-speed compressors and advanced electronic controls, enhancing overall performance and comfort.

Additionally, R410A systems often come equipped with variable refrigerant flow (VRF) technology, which allows for precise temperature control in multiple zones of a building. This versatility makes R410A an ideal choice for both residential and commercial installations, providing optimal comfort throughout various spaces.

In summary, Friedrich R410A stands out due to its high energy efficiency, zero ozone depletion potential, and suitability for modern HVAC technologies. As the industry moves towards more sustainable practices, R410A serves as a reliable refrigerant that balances performance with environmental responsibility. It’s a significant choice for anyone looking to invest in efficient and eco-friendly heating and cooling solutions.