COMPONENTS TESTING (Continued)

BLOWER / FAN MOTOR

A single phase permanent split capacitor motor is used to drive the evaporator blower and condenser fan. A self-resetting overload is located inside the motor to protect against high temperature and high amperage conditions.

WARNING

ELECTRIC SHOCK HAZARD

Disconnect power to the unit before servicing. Failure to follow this warning could result in serious injury or death.

BLOWER / FAN MOTOR TEST

1.Visually inspect the motor’s wiring, housing etc., and determine that the capacitor is serviceable.

2.Make sure the motor has cooled down.

3.Disconnect the fan motor wires from the control board.

4.Test for continuity between the windings also, test to ground.

5.If any winding is open or grounded replace the motor.

Many motor capacitors are internally fused. Shorting the terminals will blow the fuse, ruining the capacitor. A 20,000 ohm 2 watt resistor can be used to discharge capacitors safely. Remove wires from capacitor and place resistor across terminals. When checking a dual capacitor with a capacitor analyzer or ohmmeter, both sides must be tested.

Capacitor Check with Capacitor Analyzer

The capacitor analyzer will show whether the capacitor is “open” or “shorted.” It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power-factor percentage. The instrument will automatically discharge the capacitor when the test switch is released.

Capacitor Connections

The starting winding of a motor can be damaged by a shorted and grounded running capacitor. This damage usually can be avoided by proper connection of the running capacitor terminals.

From the supply line on a typical 230 volt circuit, a 115 volt potential exists from the “R” terminal to ground through a possible short in the capacitor. However, from the “S” or start terminal, a much higher potential, possibly as high as 400 volts, exists because of the counter EMF generated in the start winding. Therefore, the possibility of capacitor failure is much greater when the identifi ed terminal is connected to the “S” or start terminal. The identifi ed terminal should always be connected to the supply line, or “R” terminal, never to the “S” terminal.

When connected properly, a shorted or grounded running capacitor will result in a direct short to ground from the “R” terminal and will blow the line fuse. The motor protector will protect the main winding from excessive temperature.

CAPACITORS

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before servicing. Discharge capacitor with a 20,000 Ohm 2 Watt resistor before handling.

Failure to do so may result in personal injury, or death.

19

Image 20
Contents Single Package Vertical Air Conditioning System Table of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Introduction Property Damage Hazards00001 Serial NumberYear Manufactured Production RUN Number Product LineElectrical Requirements Chassis Specifi cations Technical Service Data Cooling Performance DataElectronic Control Board Features Quiet Start/StopHeat Mode in Cool with Electric Heat Units Compressor Lock Out Time Low Voltage Interface Connections Electric Shock HazardService CUT/SEVER HazardVpak 9-18K BTU Units Components Identification Ground Air IntakeVpak 24K BTU Units Components Identification Air Intake Front SideError Codes and Alarm Status Components Testing Fuse 10 Amps 250 VaC Capacitor Check with Capacitor Analyzer Capacitor ConnectionsBlower / FAN Motor Blower / FAN Motor TestHeater Elements and Limit SWITCHES’ Specifications Drain PAN ValveExternal Static Pressure Explanation of charts Refrigeration Assembly Refrigeration Sequence of OperationSealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Undercharged Refrigerant SystemsBurn Hazard Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemCooling Mode Heating ModeHermetic Components Check Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Fire Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Single Phase Connections Single Phase Running and L.R.A. TestLocked Rotor Voltage L.R.V. Test Determine L.R.VSingle Phase Resistance Test External Overload Vpak 9, 12, 18 K BtusInternal Overload Vpak 24 K Btus Ground TestRecommended procedure for compressor replacement High TemperaturesRoutine Maintenance Electrical Shock HazardRoom AIR Conditioner Unit Performance Test Data Sheet THERMISTORS’ Resistance Values Electrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Compressor outdoorElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart Heating Heat PumpRemote Wall Thermostat Wiring Diagrams Heat Pump with Electric HeatGH GL B Y RT6 Cool with Electric Heat 6TRGH GL B Y W R GH GL O/B Y W Wiring Diagram Heat Pump EH 5KW, 10.0KW Model Description Photo Friedrich Air Conditioning Company Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models Vpak 9K-18K BTU/h Models 9K-18K BTU/h Models Vpak Parts List Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models Vpak 24K BTU/h Models 24K BTU/h Models Vpak Parts List Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 45 pages 45.67 Kb Manual 7 pages 15.54 Kb Manual 27 pages 24.75 Kb

R410A specifications

Friedrich R410A is a refrigerant blend that has become a cornerstone in the HVAC industry, particularly for air conditioning systems. This hydrofluorocarbon (HFC) is known for its efficiency and environmentally friendly properties, making it a popular alternative to older refrigerants like R22.

One of the main features of R410A is its exceptional thermal efficiency. It has a higher cooling capacity compared to R22, which allows for smaller and more efficient equipment. This efficiency translates to reduced energy consumption and lower operating costs for users. Additionally, the higher pressure capability of R410A enables the design of more compact systems, which is particularly beneficial for residential and commercial applications where space is often limited.

R410A is characterized by its zero ozone depletion potential (ODP), which is a significant advantage over its predecessors. This makes it a more environmentally responsible choice, aligning with global initiatives to phase out substances that harm the ozone layer. However, it is essential to note that while R410A does not deplete the ozone, it does have a global warming potential (GWP) of approximately 2,088, making it less favorable in terms of climate impact compared to natural refrigerants.

In terms of technology, R410A is typically utilized in systems that are designed specifically for this refrigerant. Equipment compatible with R410A often features advanced components that can handle the higher pressures required. Many modern air conditioning systems equipped with R410A also incorporate variable-speed compressors and advanced electronic controls, enhancing overall performance and comfort.

Additionally, R410A systems often come equipped with variable refrigerant flow (VRF) technology, which allows for precise temperature control in multiple zones of a building. This versatility makes R410A an ideal choice for both residential and commercial installations, providing optimal comfort throughout various spaces.

In summary, Friedrich R410A stands out due to its high energy efficiency, zero ozone depletion potential, and suitability for modern HVAC technologies. As the industry moves towards more sustainable practices, R410A serves as a reliable refrigerant that balances performance with environmental responsibility. It’s a significant choice for anyone looking to invest in efficient and eco-friendly heating and cooling solutions.