INSTALLATION | ||
|
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
PLUGS AND HAND HELD EQUIPMENT
For further protection against electric shock, any elec- trical equipment connected to the generator recepta- cles must use a
WARNING
Never operate this machine with damaged or defective cords. All electrical equipment must be in safe operating condition.
AUXILIARY POWER RECEPTACLES
The control panel of the OUTBACK® 185 features three auxiliary power receptacles:
•Two 20 amp,120 volt duplex (double outlet) receptacle.
•A 50 amp, 240 volt single outlet receptacle.
See Figure A.1
Through these receptacles the machine can supply up to 5700 watts surge or 5200 watts continuous of single- phase 60 Hertz AC power. The machine output volt- ages meet UL standards and fall within ± 10% of the rated voltage.
PREMISES WIRING
The OUTBACK® 185 is not recommended for premis- es wiring. The OUTBACK® 185 does not have a com- bined 120/240 volt receptacle and cannot be connect- ed to a premises as described in other Lincoln litera- ture.
The OUTBACK® 185 is intended only for backup, intermittent use power. Certain electrical devices can- not be powered by the OUTBACK® 185. Refer to Table A.2 for these devices.
CIRCUIT BREAKERS
Auxiliary power is protected by circuit breakers. When the machine is operated in high temperature environ- ments, the breakers may tend to trip at lower loads than normally.
CAUTION
NEVER BYPASS THE CIRCUIT BREAKERS. WITH- OUT OVERLOAD PROTECTION, THE UNIT COULD OVERHEAT AND/OR CAUSE DAMAGE TO THE EQUIPMENT BEING USED.
OUTBACK® 185