INSTALLATION | ||
|
|
|
AUXILIARY POWER RECEPTACLES
Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the receptacles for auxiliary power. This must be done before a tripped GFCI receptacle can be reset proper- ly. See the MAINTENANCE section for detailed infor- mation on testing and resetting the GFCI receptacle.
The auxiliary power of the RANGER 305 LPG con- sists of two 20
The auxiliary power capacity is 9,000 Watts Peak, 8000 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equiva- lent to
The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the cur- rent capacity of the associated receptacle.
NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.
STANDbY POWER CONNECTIONS
The RANGER® 305LPG is suitable for temporary, standby or emergency power using the engine manufacturer’s rec- ommended maintenance schedule.
The RANGER® 305LPG can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 40 amp service. Connections must be made by a licensed elec- trician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.
•Install the
•Take necessary steps to assure load is limited to the capacity of the RANGER® 305LPG by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 40 amperes. Loading above the rated output will reduce out- put voltage below the allowable - 10% of rated voltage which may damage appliances or other
•Install a 50 amp, 120/240 VAC plug (NEMA Type
•Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER® 305LPG case front.
RANGER® 305LPG