Lincoln Electric IM927 manual Welder Operation, Auxiliary Power

Page 13

A-6

INSTALLATION

A-6

 

 

 

WELDER OPERATION

WELDER OUTPUT

Maximum Open Circuit Voltage at 3700 RPM is 80 Volts RMS.

Duty Cycle is the percentage of time the load is being applied in a 10 minute period. For example, a 60% duty cycle represents 6 minutes of load and 4 minutes of no load in a 10 minute period. Duty Cycle for the WELDMARK 225 is 100%.

WELDMARK 225

Constant Current

225 Amps AC @ 25 Volts

 

 

210 Amps DC @ 25 Volts

 

 

 

Constant Voltage

200 Amps DC @ 20 Volts

 

 

 

AUXILIARY POWER

The WELDMARK 225 can provide up to 9,000 watts of 120/240 volts AC, single phase 60Hz power for continuous use, and up to 10,500 watts of 120/240 volts AC, single phase 60Hz power peak use. The front of the machine includes three receptacles for connecting the AC power plugs; one 50 amp 120/240 volt NEMA 14-50R receptacle and two 20 amp 120 volt NEMA 5-20R receptacles. Output voltage is with- in +/-10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers. All auxiliary power is protected by circuit breakers.

120/240 VOLT DUAL VOLTAGE RECEPTACLE

The 120/240 volt receptacle can supply up to 38 amps of 240 volt power to a two wire circuit, up to 38 amps of 120 volts power from each side of a three wire cir- cuit (up to 76 amps total). Do not connect the 120 volt circuits in parallel. Current sensing for the automatic idle feature is only in one leg of the three wire circuit as shown in the following column.

GND

120 V

240 V

120 V*

*Current Sensing for Automatic Idle. (Receptacle viewed from front of Machine)

120 V DUPLEX RECEPTACLES

The 120V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs.

The current rating of any plug used with the system must be at least equal to the current load through the associated receptacle.

MOTOR STARTING

CAUTION

Do not connect any plugs that connect to the power receptacles in parallel.

-----------------------------------------------------------------------

Start the engine and set the “IDLER” control switch to the desired operating mode. Set the “CONTROL” to

10.Voltage is now correct at the receptacles for auxil- iary power.

Most 1.5 hp AC single phase motors can be started if there is no load on the motor or other load connected to the machine, since the full load current rating of a

1.5hp motor is approximately 20 amperes (10 amperes for 240 volt motors). The motor may be run at full load when plugged into only one side of the duplex receptacle. Larger motors through 2 hp can be run provided the receptacle rating as previously stated is not exceeded. This may necessitate 240V operation only.

WELDMARK 225 Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

Current

Voltage

Load

 

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

 

 

(Amps)

Volts

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(12)

75

(23)

125

(38)

175

(53)

300

(91)

20

120

2400

 

 

30

(9)

50

(15)

88

(27)

138

(42)

225

(69)

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

20

240

4800

 

 

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

38

240

9000

 

 

 

 

50

(15)

90

(27)

150

(46)

225

(69)

 

 

 

 

Conductor size is based on maximum 2.0% voltage drop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WELDMARK 225

Image 13
Contents Weldmark Safety Depends on YouWeldmark SafetyElectric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéA n k Table of Contents Auxiliary Power InstallationHeight Width Depth Weight Welding OutputMachine Grounding Safety PrecautionsSpark Arrester TowingBattery Connections PRE-OPERATION ServiceGasoline Fuel only Vehicle MountingTotal Combined Length of Electrode and Work Cables Welding Output CablesAngle of Operation LiftingAdditional Safety Precautions Connection of Lincoln Electric Wire FeedersInstructions Location / VentilationWelder Operation Auxiliary PowerType Common Electrical Devices Possible Concerns Electrical Device USE with the WeldmarkSimultaneous Welding and Power Auxiliary Power While WeldingStandby Power Connections WELDMARK225Connection of Weldmark 225 to Premises Wiring Operation Engine SwitchGENERAL DESCRIPTION Welder Controls Function and OperationWeldmark 225 Approximate Fuel Consumption Polarity SwitchBREAK-IN Period STARTING/SHUTDOWN InstructionsStarting the Engine Stopping the EngineWelding Process Wire Feed Welding Processes Constant VoltageStick Constant Current Welding TIG Constant Current WeldingStick Auto Optional Equipment Field Installed AccessoriesWIRE FEED 2ACCESSORIESC-2RECOMMENDED EQUIPMENT StickSafety Precautions MaintenanceRoutine Maintenance Engine OIL ChangeOIL Filter Change AIR Cleaner and Other MaintenanceBattery Engine Adjustments Overspeed is HazardousEngine Maintenance Parts Slip RingsHOW to USE Troubleshooting Guide TroubleshootingTroubleshooting Troubleshooting Wiring Diagrams Warni NG DiagramsWeldmark 225 Kohler Dimension PrintPrecaucion Warnung Weldmark