Lincoln Electric 500 manual Auxiliary Power Receptacles Standby Power Connections

Page 15

A-7

INSTALLATION

A-7

AUXILIARY POWER RECEPTACLES

STANDBY POWER CONNECTIONS

 

Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the recepta- cles for auxiliary power. This must be done before a tripped GFCI module can be reset properly. See the MAINTENANCE section for more detailed information on testing and resetting the GFCI module.

The auxiliary power of the VANTAGE® 500 consists of two 20 Amp-120 VAC (5-20R) duplex receptacles with GFCI protection, one 50 Amp 120/240 VAC (14-50R) receptacle and one 50 Amp 240VAC Three-Phase (15- 50R) receptacle.

The VANTAGE® 500 is suitable for temporary, stand- by or emergency power using the engine manufactur- er’s recommended maintenance schedule.

The VANTAGE® 500 can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 50 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

The auxiliary power capacity is 13,000 watts Peak, 12,000 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equivalent to volt-amperes at unity power factor. The max permissi- ble current of the 240 VAC output is 50amps.

The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 50 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity.

The Three-Phases auxiliary power capacity is 22,000 watts peak, 20,000 watts continuous. The maximum cur- rent is 45 amps.

120 V DUPLEX RECEPTACLES AND GFCI MODULES

A GFCI Module protects the two 120V auxiliary power receptacles.

A GFCI (Ground Fault Circuit Interrupter) is a device to protect against electric shock should a piece of defective equipment connected to it develop a ground fault. If this situation should occur, the GFCI module will trip, remov- ing voltage from the output of the receptacle. If a GFCI module is tripped see the MAINTENANCE section for detailed information on testing and resetting it. A GFCI module should be properly tested at least once every month.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated recepta- cle.

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.

All auxiliary power is protected by circuit breakers. The 120V has 20 Amp circuit breakers for each duplex recep- tacle. The 120/240V Single Phase and the 240V Three- Phases have a 50 Amp 3-pole Circuit Breaker that dis- connects both hot leads and all Three Phases simultane- ously.

Install the double - pole, double - throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

Take necessary steps to assure load is limited to the capacity of the generator by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amperes. Loading above the rated output will reduce output voltage below the allowable - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the engine and/or alternator wind- ings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50P) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt recep- tacle on the case front.

WARNING

Only a licensed, certified, trained electrician should install the machine to a premises or resi- dential electrical system. Be certain that:

The installation complies with the National Electrical Code and all other applicable electri- cal codes.

The premises is isolated and no feedback into the utility system can occur. Certain laws require

the premises to be isolated before the generator is linked to the premises. Check your local requirements.

------------------------------------------------------------------------

VANTAGE® 500

Image 15
Contents Vantage California Proposition 65 Warnings SafetyE C T R I C S H O C K c a n kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéThank You Table of Contents Section D Section ESection F Technical Specifications Vantage 500 K2686 InstallationReceptacles Auxiliary Power Circuit Breaker Other Circuit BreakersSafety Precautions VRD Voltage Reduction DeviceLocation and Ventilation OIL PRE-OPERATION Engine ServiceVehicle Mounting TowingEngine Cooling System Battery ConnectionRemote Control FuelElectrical Connections Duplex Receptacles and Gfci Modules Auxiliary Power Receptacles Standby Power ConnectionsConnection of Vantage 500 to Premises Wiring Control Cable Model Connection of Lincoln Electric Wire FeedersConnection of LN-15 to the Vantage Shut the welder off Across The-Arc ModelInstallation General Description OperationFigure B.1 Weld Mode Selector SwitchTable B.1 Wire Feeder Voltmeter SwitchTable B.2 Engine ControlsGlow Plug Push Button Starting the EngineDuty Cycle Stopping the EngineWelder Operation Constant Current CC-STICK WeldingTIG Welding Typical Current Ranges 1 for Tungsten ELECTRODES2Table B.3 Plus Wire WELDING-CVAuxiliary Power ARC GougingAccessories Field Installed OptionsWelders Vantage Routine Maintenance MaintenanceSuch as dust and dirt being drawn into the engine AIR CleanerEngine OIL Change OIL Filter ChangeService Instructions Cooling System Tightening the FAN BeltBleeding the Fuel System Engine Adjustment Battery MaintenanceServicing Optional Spark Arrestor Gfci Module Testing and Resetting Procedure Welder / Generator MaintenanceHOW to USE Troubleshooting Guide TroubleshootingContact your local Lincoln Welding without a control cable Authorized Field Service Facility Authorized Field Service Facility Your local Lincoln Authorized Field Service FacilityDiagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Wiring Diagram500 Dimension Print Vantage Vantage Aviso DE Keep your head out of fumes Turn power off before servicing
Related manuals
Manual 54 pages 2.58 Kb Manual 56 pages 23.87 Kb

500 specifications

The Lincoln Electric 500 is a hallmark of innovation in arc welding technology, designed to cater to the rigorous demands of both industrial applications and serious hobbyist projects. This powerful machine is known for its reliability, versatility, and user-friendly design, making it an essential tool for professional welders and those looking to tackle various welding tasks with ease.

One of the standout features of the Lincoln Electric 500 is its robust power output. With a capability of up to 500 amps, it can handle a wide range of welding processes, including Stick, TIG, and MIG welding. This flexibility allows welders to use the machine for different types of metals, including steel, stainless steel, and aluminum, making it suitable for diverse applications from automotive to construction industries.

The machine's digital interface enhances user experience by providing precise control over the welding parameters. The intuitive display allows for easy adjustments of voltage and wire speed, ensuring optimal welding conditions are achieved. This feature is especially beneficial for beginners who may require additional support as they learn the intricacies of welding.

The Lincoln Electric 500 is also equipped with advanced technologies that enhance efficiency and welding quality. One such technology is the inverter system, which optimizes the power source for superior arc stability and improved penetration. This results in cleaner welds with minimal spatter, reducing the need for post-welding cleanup. Furthermore, the machine’s duty cycle is impressive, meaning it can operate for extended periods without overheating, a critical factor in high-production environments.

Another significant characteristic of the Lincoln Electric 500 is its portability. Weighing in at a manageable level and designed with built-in carrying handles, it’s easy to transport between job sites. This feature is particularly valuable for mobile welders who need to work in various locations.

Safety is paramount in welding operations, and the Lincoln Electric 500 integrates various safety features designed to protect the user. Overload protection and thermal overload indicators help prevent damage to the machine and injury to the operator, ensuring a reliable and safe working environment.

Overall, the Lincoln Electric 500 stands out not only for its performance but also for its thoughtful engineering that prioritizes user safety, comfort, and versatility. It is a dependable choice for anyone looking to produce high-quality welds while enjoying the benefits of advanced welding technology.