Friedrich 2008, 2009 service manual To start unit, To adjust temperature 60F 16C to 90F 32C

Page 14

How to operate the Friedrich room air conditioner (QuietMaster Programmable)

To start unit

1If your air conditioner is installed and plugged into a proper re- ceptacle, it is ready to go. Touch Power button once. The unit will automatically be in Cool mode with the temperature set at 75°F (24°C) and the fan speed at F1, the sleep setting. There is a 3- minute delay before the compressor will turn on. (See "Automatic Component Protection" on this page).

2Should the Check Filter light turn on when you rst turn on the unit, touch Check Filter to turn off the light. Check Filter light will come on after 250 hours of use. Clean filter.

Touch Check Filter to reset.

To set mode of operation

3When you rst turn on the unit, it will be in the Cool mode (light on), with constant fan.

4Touch MoneySaver® (light on) to activate the MoneySaver® feature. This cycles the fan with the compressor so that the fan does not run all the time. This saves energy and improves dehumidication. (MoneySaver® will also run the fan to sample the return air tempera- ture if the off cycle is too long). Or you may prefer constant fan for more air movement. To return to constant fan, touch Cool.

5Touch Fan Only (light on) if you want only the fan to run. You may want to use this feature in conjunction with the Fresh Air / Exhaust lever to bring outside air into a room, or to exhaust stale air. (See page 7, "Fresh Air and Exhaust Control" for more information.)

To adjust temperature [60°F (16°C) to 90°F (32°C)]

6COOLER – Touch and hold until the display shows the desired room temperature.

7WARMER – Touch and hold until the display shows the desired room temperature.

8FAHRENHEIT / CELSIUS – Touch ºF / ºC to show the temperature in Celsius, touch again to show Fahrenheit.

To adjust fan speed

9Touch 1-4 Speed to see current setting. Touch again to change speed. F1 is the lowest setting (SLEEP SETTING), F2 is low speed (LOW), F3 is medium speed (MED), F4 is high speed (HIGH).

To activate smart fan

10Touch Smart Fan (light on). Smart Fan will adjust the fan speed automatically to maintain the desired comfort level. For example, if the outside doors in your home are open for an extended period of time, or more people enter a room, Smart Fan may adjust to a higher fan speed to compensate for the increased heat load. This keeps you from having to adjust the fan speed on your own. Smart Fan cannot be activated in the Fan Only mode.

To deactivate smart fan

11 Touch 1-4 Speed, and select your desired fan speed.

Figure 3

PM

DISPLAY

 

 

Set

Check

2

 

 

 

 

Hour

Filter

 

 

 

 

 

 

 

 

 

 

Press to reset

12

 

 

 

 

 

 

1

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

3

 

 

 

Money

Fan

 

 

 

 

Cool

5

 

 

Mode

Saver®

Only

 

 

 

 

 

 

6

 

 

 

 

OF/ OC

8

 

 

Temp

 

 

 

 

 

 

 

7

9

11

 

 

 

 

 

1-4

Smart

 

 

 

 

Fan

Speed

Fan

 

10

 

 

 

 

 

 

 

 

 

 

 

 

14

13

 

 

A/C

A/C

Timer

 

 

 

 

15

 

 

Timer

Stop

Start

On/O￿

 

 

 

 

 

 

To set the timer

NOTE: Set Hour clock before attempting to set timer functions.

You can set the A/C Start and A/C Stop timer a minimum of one hour apart and a maximum of 23 hours apart.

13TIMER STOP - Press the A/C Stop button and continue pressing until the hour you want the unit to shut off appears in the display (A.M. or P.M.). The stop time for cooling will then be set.

14START TIME - Press A/C Start to view the current start time for cooling. Continue pressing until the hour you want the unit to start appears in the display (A.M. or P.M.). The start time for cooling will then be set.

15Press the Timer On/ Off button once to activate (light on) the timer function. Touch Timer On/ Off again (light off) to cancel the timer function if you so desire. Once the on and off times have been se- lected, they will remain in memory, and cycle daily until changed.

NOTE: If unit is unplugged or power is interrupted, the Set Hour button must be reset or the Timer On/ Off functions will not work.

To set hour clock

12Press Set Hour once to see the current clock setting. Continue pressing the button until the hour closest to the actual time appears in the display.

MAKE SURE YOU SET A.M. AND P.M. PROPERLY. A light will appear in the upper left corner of the display when the hour is P.M.

NOTE: Minutes will NOT show on display.

Automatic component protection

Your unit is equipped with Automatic Component Protection.

To protect the compressor of the unit, there is a three minute time delay if you turn the unit off or if power is interrupted. The fan will not be affected.

12

Image 14
Contents Room Air Conditioners Technical Support Contact Information Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Property Damage Hazards Introduction Typical Unit Components7th Digit Options 0 = Straight Cool & Heat Pump Models 1st Digit Function2nd Digit 6th Digit Voltage 1 = 115 VoltsChassis Specifications for 2009, 2008 models Installation information / sleeve dimensions Performance Data for 2009, 2008 models Electric Shock Hazard Fire HazardMake sure the wiring is adequate for your unit To adjust temperature 60F 16C to 90F 32C To start unitHow to use the remote control* QuietMaster Programmable How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models How to operate the Friedrich room air conditioner Activating Test Mode Testing the Electronic Control Boards for QME & XQ ModelsChecking Room Temperature Testing the Electronic Control Error Code Listings Testing the Rotary Control Switches KS, KM, SL Models See FigureMechanical Components EQ08 System Control Switch TestFunctional Component Definitions Electrical ComponentsTest Components TestingThermostat Adjustment Thermostat Bulb LocationDefrost Bulb Location Heat Pump Models Resistor Heat Anticipator See FigureDefrost Thermostat Heat Pump Models Only Capacitor Connections CapacitorsCapacitor Check with Capacitor Analyzer FAN MotorHeating Element Heat Pump Models Testing the Heating Element Electric Shock HazardHeating Element See Figure Drain PAN ValveOperating Sequence / Characteristics and Features Smart FANRefrigeration Sequence of Operation Equipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Check Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Checking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Rotary Compressor Special Troubleshooting and Service Blower Wheel / Housing / Condenser FAN / Shroud Routine MaintenanceCoils and Base PAN Excessive Weight Hazard AIR FilterSleeve / Drain Front CoverCooling only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause ActionReplace fuse, reset breaker. If repeats, check Fused separately Problem Possible Cause Action Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat / Cool Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionYES System Cools When Heating is DesiredHeat Pump Normal Function of Valve Malfunction of ValveElectronic Control Cool only Models Electronic Control Cool only Models Electromechanical Control Cool only Models SL28L30-D,-E SL36L30A-D,A-E Page Electromechanical Control Cool with Electric Heat Models EL36L35A-D,A-E Electromechanical Control Heat Pump only Models YS13L33-D,-E YM18L34-D,-E YL24L35-E,-F Aham PUB. NO. RAC-1 DAY Cooling Load Estimate FormHeat Gain from Quantity Factors Following is an example using the heat load form Heat Load FormWindows & Doors Area, sq. ft Infiltration Windows & Doors AVGRoom AIR Conditioners Limited Warranty Page Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 60 pages 54.38 Kb Manual 60 pages 45.7 Kb

2009, 2008 specifications

Friedrich 2008 and 2009 represent significant advancements in heating and cooling technology, particularly in the realm of air conditioning systems. Friedrich is known for producing robust and efficient HVAC solutions tailored for both residential and commercial applications. These models are particularly noteworthy for their innovative features and energy-efficient technologies that enhance user comfort and lower operational costs.

One of the main characteristics of the Friedrich 2008 and 2009 models is their emphasis on energy efficiency. Both units are designed to meet or exceed Energy Star standards, which indicates that they use less energy compared to standard models, contributing to greener living solutions. The incorporation of efficient compressors and high SEER (Seasonal Energy Efficiency Ratio) ratings ensures that users save money on their electricity bills while enjoying optimal cooling performance.

The units also feature advanced inverter technology, which allows for variable speed operation. This means that the system can adjust its cooling capacity based on the current temperature needs, resulting in more consistent comfort while reducing wear and tear on the equipment. Additionally, the inverter technology operates more quietly compared to traditional systems, making these models suitable for both home environments and commercial settings.

Friedrich 2008 and 2009 also provide users with enhanced control options. The inclusion of smart technology and Wi-Fi connectivity allows for remote monitoring and temperature adjustments via smartphones or tablets. Users can create schedules, set temperature preferences, and receive maintenance alerts, contributing to a more user-friendly experience.

Moreover, these models are designed with robust construction, featuring durable materials that withstand various weather conditions. Their compact footprint and sleek design make them suitable for window installation, while an array of sizes accommodates spaces of different dimensions.

Additionally, the air filtration systems in Friedrich 2008 and 2009 units improve indoor air quality. They effectively capture dust, allergens, and other particulates, ensuring a healthier environment for occupants.

In summary, Friedrich 2008 and 2009 models stand out for their energy efficiency, innovative inverter technology, smart controls, and robust construction. With a focus on user comfort and environmental responsibility, these models provide reliable solutions for effective heating and cooling in diverse applications.