Friedrich 2008, 2009 service manual Testing the Electronic Control Error Code Listings

Page 20

Activating Error Code Mode: (Submode of Test Mode) Unit must be in Test Mode to enter Error Code Mode

1.Activate Error Code Mode by pressing the “TIMER ON/ OFF” button on XQ models. LED for the “TIMER ON/ OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP/HR button will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP/HR button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

Activate Error Code Mode by pressing at the same time the “A/C START” button and the “ON/OFF” button on QME models. LED for the “TIMER ON/OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP button will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

IMPORTANT: Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ models, press Timer On/Off button. To exit QME models, press A/C Start and On/Off buttons. Or unplug unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit.

TESTING THE ELECTRONIC CONTROL ERROR CODE LISTINGS

E1 SHORT CYCLE SITUATION: Defined as (compressor powered on before the three minute time delay ten times in one hour. Investigate and correct short cycling problem.

E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error “E2” is no longer displayed and unit is functioning. Replace board if “E2” still displays after exiting Error Code Mode.

E3 FROST PROBE OPEN: Normal operation is allowed. Ohm frost probe. Replace probe if ohm value not read. If ohm value is present replace board.

E4 FROST PROBE SHORT: Normal operation allowed. Replace probe.

E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degree F and unit will operate. Ohm indoor probe. Replace probe if ohm value not read.

E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degree F and unit will operate. Replace probe.

NOTE: All Error Code displays for Frost & Indoor Probe will allow unit to operate. Unit may or will ice up if faulty components not replaced.

FROST PROBE SENSOR: disables compressor at 35 degrees F.

INDOOR PROBE SENSOR: Control range is 60 degrees F to 90 degrees F +/- 2 degrees F.

Indoor temperature will be displayed by pressing: (QME units) The Fan Speed button and the Temperature button.

(XQ units) The Fan Speed button and the “TEMP “ button.

The indoor temperature will be displayed for 10 seconds. The display will change back to the Set Point temperature by pressing any key button except for the On/Off button. The indoor temperature can be viewed in all modes, including test mode.

Check Filter: The Check Filter indicator turns on after the fan motor has been operating for 250 hours. The Check Filter indicator is reset by pressing the Check Filter button one time only. Power failures will not reset the 250 hour timer. All time elapsed is stored in memory and resumes counting after power is restored.

Keep Alive: The electronic control has a memory to retain all functions and status as set up by the user in the event of a power failure. Once power is restored to the unit there is a two second delay before the fan comes on and approximately three minutes delay before the compressor is activated, providing that the mode was set for cooling and the set point temperature has not been met in the room.

18

Image 20
Contents Room Air Conditioners Technical Support Contact Information Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Property Damage Hazards Introduction Typical Unit Components1st Digit Function 2nd Digit7th Digit Options 0 = Straight Cool & Heat Pump Models 6th Digit Voltage 1 = 115 VoltsChassis Specifications for 2009, 2008 models Installation information / sleeve dimensions Performance Data for 2009, 2008 models Electric Shock Hazard Fire HazardMake sure the wiring is adequate for your unit To adjust temperature 60F 16C to 90F 32C To start unitHow to use the remote control* QuietMaster Programmable How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models How to operate the Friedrich room air conditioner Activating Test Mode Testing the Electronic Control Boards for QME & XQ ModelsChecking Room Temperature Testing the Electronic Control Error Code Listings Testing the Rotary Control Switches KS, KM, SL Models See FigureEQ08 System Control Switch Test Functional Component DefinitionsMechanical Components Electrical ComponentsComponents Testing Thermostat AdjustmentTest Thermostat Bulb LocationDefrost Bulb Location Heat Pump Models Resistor Heat Anticipator See FigureDefrost Thermostat Heat Pump Models Only Capacitors Capacitor Check with Capacitor AnalyzerCapacitor Connections FAN MotorTesting the Heating Element Electric Shock Hazard Heating Element See FigureHeating Element Heat Pump Models Drain PAN ValveOperating Sequence / Characteristics and Features Smart FANRefrigeration Sequence of Operation Sealed Refrigeration System Repairs Equipment RequiredEquipment Must be Capable Risk of Electric ShockFreeze Hazard Method Of Charging / RepairsBurn Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Hermetic Components Check Metering DeviceCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveExplosion Hazard Procedure For Changing Reversing ValveTouch Test in Heating/Cooling Cycle Compressor Checks Checking Compressor Efficiency Single Phase Resistance TestGround Test High Temperatures Compressor ReplacementRecommended procedure for compressor replacement Rotary Compressor Special Troubleshooting and Service Routine Maintenance Coils and Base PAN Excessive Weight HazardBlower Wheel / Housing / Condenser FAN / Shroud AIR FilterSleeve / Drain Front CoverCooling only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause ActionReplace fuse, reset breaker. If repeats, check Fused separately Problem Possible Cause Action Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat / Cool Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionYES System Cools When Heating is DesiredHeat Pump Normal Function of Valve Malfunction of ValveElectronic Control Cool only Models Electronic Control Cool only Models Electromechanical Control Cool only Models SL28L30-D,-E SL36L30A-D,A-E Page Electromechanical Control Cool with Electric Heat Models EL36L35A-D,A-E Electromechanical Control Heat Pump only Models YS13L33-D,-E YM18L34-D,-E YL24L35-E,-F Aham PUB. NO. RAC-1 DAY Cooling Load Estimate FormHeat Gain from Quantity Factors Following is an example using the heat load form Heat Load FormWindows & Doors Area, sq. ft Infiltration Windows & Doors AVGRoom AIR Conditioners Limited Warranty Page Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 60 pages 54.38 Kb Manual 60 pages 45.7 Kb

2009, 2008 specifications

Friedrich 2008 and 2009 represent significant advancements in heating and cooling technology, particularly in the realm of air conditioning systems. Friedrich is known for producing robust and efficient HVAC solutions tailored for both residential and commercial applications. These models are particularly noteworthy for their innovative features and energy-efficient technologies that enhance user comfort and lower operational costs.

One of the main characteristics of the Friedrich 2008 and 2009 models is their emphasis on energy efficiency. Both units are designed to meet or exceed Energy Star standards, which indicates that they use less energy compared to standard models, contributing to greener living solutions. The incorporation of efficient compressors and high SEER (Seasonal Energy Efficiency Ratio) ratings ensures that users save money on their electricity bills while enjoying optimal cooling performance.

The units also feature advanced inverter technology, which allows for variable speed operation. This means that the system can adjust its cooling capacity based on the current temperature needs, resulting in more consistent comfort while reducing wear and tear on the equipment. Additionally, the inverter technology operates more quietly compared to traditional systems, making these models suitable for both home environments and commercial settings.

Friedrich 2008 and 2009 also provide users with enhanced control options. The inclusion of smart technology and Wi-Fi connectivity allows for remote monitoring and temperature adjustments via smartphones or tablets. Users can create schedules, set temperature preferences, and receive maintenance alerts, contributing to a more user-friendly experience.

Moreover, these models are designed with robust construction, featuring durable materials that withstand various weather conditions. Their compact footprint and sleek design make them suitable for window installation, while an array of sizes accommodates spaces of different dimensions.

Additionally, the air filtration systems in Friedrich 2008 and 2009 units improve indoor air quality. They effectively capture dust, allergens, and other particulates, ensuring a healthier environment for occupants.

In summary, Friedrich 2008 and 2009 models stand out for their energy efficiency, innovative inverter technology, smart controls, and robust construction. With a focus on user comfort and environmental responsibility, these models provide reliable solutions for effective heating and cooling in diverse applications.