Friedrich 2009, 2008 service manual Aham PUB. NO. RAC-1

Page 61

INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE

FORM FOR ROOM AIR CONDITIONERS

(AHAM PUB. NO. RAC-1)

A.This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations which do not require specifi c conditions of inside temperature and humidity.

B.The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas in the continental United States having other outside design temperatures by applying a correction factor for the particular locality as determined from the map.

C.The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as living rooms, offi ces, etc.)

D.The numbers of the following paragraphs refer to the corresponding numbered item on the form:

1.Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for “Inside Shades.” For windows shaded by outside awnings or by both outside aw- nings and inside shades (or venetian blinds), use the factor for “Outside Awnings.” “Single Glass” includes all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows, and glass block. Only one number should be entered in the right hand column for Item 1, and this number should represent only the exposure with the largest load.

2.Multiply the total square feet of all windows in the room by the applicable factor.

3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should be considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered “North Exposure.” Do not consider trees and shrubbery as providing permanent shading. An uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.” An insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.”

3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any uncondi- tioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.

4.Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application (use one line only.)

5.Multiply the total square feet of fl oor area by the factor given. Disregard this item if the fl oor is directly on the ground or over a basement.

6.Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use a minimum of 2 people.

7.Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.

8.Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor.

NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis.

9.Total the loads estimated for the foregoing 8 items.

10.Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour.

E.For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance with the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously.

F.Intermittent loads such as kitchen and laundry equipment are not included in this form.

4

59

Image 61
Contents Room Air Conditioners Technical Support Contact Information Table Of Contents Your safety and the safety of others are very important Important Safety InformationRefrigeration System Hazards Property Damage Hazards Typical Unit Components Introduction2nd Digit 1st Digit Function7th Digit Options 0 = Straight Cool & Heat Pump Models 6th Digit Voltage 1 = 115 VoltsChassis Specifications for 2009, 2008 models Installation information / sleeve dimensions Performance Data for 2009, 2008 models Fire Hazard Electric Shock HazardMake sure the wiring is adequate for your unit To start unit To adjust temperature 60F 16C to 90F 32CHow to use the remote control* QuietMaster Programmable How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models How to operate the Friedrich room air conditioner Checking Room Temperature Testing the Electronic Control Boards for QME & XQ ModelsActivating Test Mode Testing the Electronic Control Error Code Listings KS, KM, SL Models See Figure Testing the Rotary Control SwitchesFunctional Component Definitions EQ08 System Control Switch TestMechanical Components Electrical ComponentsThermostat Adjustment Components TestingTest Thermostat Bulb LocationDefrost Thermostat Heat Pump Models Only Resistor Heat Anticipator See FigureDefrost Bulb Location Heat Pump Models Capacitor Check with Capacitor Analyzer CapacitorsCapacitor Connections FAN MotorHeating Element See Figure Testing the Heating Element Electric Shock HazardHeating Element Heat Pump Models Drain PAN ValveSmart FAN Operating Sequence / Characteristics and FeaturesRefrigeration Sequence of Operation Equipment Required Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Metering Device Hermetic Components CheckCheck Valve Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Checking the Reversing Valve Testing the CoilTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Coils and Base PAN Excessive Weight Hazard Routine MaintenanceBlower Wheel / Housing / Condenser FAN / Shroud AIR FilterFront Cover Sleeve / DrainProblem Possible Cause Action Cooling only Room AIR Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check Fused separately Problem Possible Cause Action Heat / Cool only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause Action Heat / Cool Room AIR Conditioners Trouble Shooting TipsHeat Pump System Cools When Heating is DesiredYES Malfunction of Valve Normal Function of ValveElectronic Control Cool only Models Electronic Control Cool only Models Electromechanical Control Cool only Models SL28L30-D,-E SL36L30A-D,A-E Page Electromechanical Control Cool with Electric Heat Models EL36L35A-D,A-E Electromechanical Control Heat Pump only Models YS13L33-D,-E YM18L34-D,-E YL24L35-E,-F Aham PUB. NO. RAC-1 Heat Gain from Quantity Factors Cooling Load Estimate FormDAY Heat Load Form Following is an example using the heat load formInfiltration Windows & Doors AVG Windows & Doors Area, sq. ftRoom AIR Conditioners Limited Warranty Page Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 60 pages 54.38 Kb Manual 60 pages 45.7 Kb

2009, 2008 specifications

Friedrich 2008 and 2009 represent significant advancements in heating and cooling technology, particularly in the realm of air conditioning systems. Friedrich is known for producing robust and efficient HVAC solutions tailored for both residential and commercial applications. These models are particularly noteworthy for their innovative features and energy-efficient technologies that enhance user comfort and lower operational costs.

One of the main characteristics of the Friedrich 2008 and 2009 models is their emphasis on energy efficiency. Both units are designed to meet or exceed Energy Star standards, which indicates that they use less energy compared to standard models, contributing to greener living solutions. The incorporation of efficient compressors and high SEER (Seasonal Energy Efficiency Ratio) ratings ensures that users save money on their electricity bills while enjoying optimal cooling performance.

The units also feature advanced inverter technology, which allows for variable speed operation. This means that the system can adjust its cooling capacity based on the current temperature needs, resulting in more consistent comfort while reducing wear and tear on the equipment. Additionally, the inverter technology operates more quietly compared to traditional systems, making these models suitable for both home environments and commercial settings.

Friedrich 2008 and 2009 also provide users with enhanced control options. The inclusion of smart technology and Wi-Fi connectivity allows for remote monitoring and temperature adjustments via smartphones or tablets. Users can create schedules, set temperature preferences, and receive maintenance alerts, contributing to a more user-friendly experience.

Moreover, these models are designed with robust construction, featuring durable materials that withstand various weather conditions. Their compact footprint and sleek design make them suitable for window installation, while an array of sizes accommodates spaces of different dimensions.

Additionally, the air filtration systems in Friedrich 2008 and 2009 units improve indoor air quality. They effectively capture dust, allergens, and other particulates, ensuring a healthier environment for occupants.

In summary, Friedrich 2008 and 2009 models stand out for their energy efficiency, innovative inverter technology, smart controls, and robust construction. With a focus on user comfort and environmental responsibility, these models provide reliable solutions for effective heating and cooling in diverse applications.