Friedrich 2008, 2009 service manual Problem Possible Cause Action

Page 46

COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Action

 

Sublimation:

Ensure that foam gaskets are installed in

 

When unconditioned saturated,

between window panes & in between the

 

outside air mixes with conditioned

unit & the sleeve. Also, ensure that fresh

 

air, condensation forms on the

air/exhaust vents (on applicable models) are in

Water “spitting”

cooler surfaces

the closed position & are in tact

into room

Downward pitch of installation is

Follow installation instructions to ensure that

 

downward pitch of installed unit is no less than

 

too steep towards back of unit

 

1/4” & no more than 3/8”

 

 

 

Restricted coil or dirty filter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Action

 

Insufficient air circulation thru area

Adjust louvers for best possible air circulation

 

to be air conditioned

Excessive

 

Oversized unit

Operate in “MoneySaver” position

moisture

Inadequate vapor barrier in building

Advise customer

 

 

structure, particularly floors

 

 

Problem

Possible Cause

Action

 

Defective thermistor

Replace thermistor or electronic control board

 

T-stat differential too narrow

Replace t-stat

T-stat or

Plenum gasket not sealing,

Check gasket. Reposition or replace as

thermistor

allowing discharge air to short

needed

short cycles

cycle t-stat

 

 

Restricted coil or dirty filter

Clean & advise customer of periodic cleaning

 

& maintenance needs of entire unit

 

 

Problem

Possible Cause

Action

 

Heat anticipator (resistor) wire

 

 

disconnected at t-stat or system

Refer to appropriate wiring diagram

 

switch

 

 

 

Disconnect plus from outlet. Remove resistor

Prolonged off

Heat anticipator (resistor) shorted or

from bracket. Insert plug & depress “COOL”

cycles (automatic

& “FAN AUTOMATIC” buttons. Place t-stat to

open

operation)

 

warmest setting. Feel resistor for temperature.

 

 

If no heat, replace resistor

 

Partial loss of charge in t-stat bulb

Replace t-stat

 

causing a wide differential

 

 

 

Defective thermistor

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Action

 

Evaporator drain pan cracked or

Repair, clean or replace as required

 

obstructed

 

 

 

Water in compressor area

Detach shroud from pan & coil. Clean &

Outside water

remove old sealer. Reseal, reinstall & check

 

leaks

Obstructed condenser coil

Use pressure wash or biodegradable cleaning

 

agent to clean

 

 

 

Fan blade/slinger ring improperly

Adjust fan blade to 1/2” of condenser coil fin

 

positioned

pack

44

Image 46
Contents Room Air Conditioners Technical Support Contact Information Table Of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Property Damage Hazards Introduction Typical Unit Components7th Digit Options 0 = Straight Cool & Heat Pump Models 1st Digit Function2nd Digit 6th Digit Voltage 1 = 115 VoltsChassis Specifications for 2009, 2008 models Installation information / sleeve dimensions Performance Data for 2009, 2008 models Electric Shock Hazard Fire HazardMake sure the wiring is adequate for your unit To adjust temperature 60F 16C to 90F 32C To start unitHow to use the remote control* QuietMaster Programmable How to operate the Friedrich room air conditioner XQ models How to use the remote control XQ models How to operate the Friedrich room air conditioner Checking Room Temperature Testing the Electronic Control Boards for QME & XQ ModelsActivating Test Mode Testing the Electronic Control Error Code Listings Testing the Rotary Control Switches KS, KM, SL Models See FigureMechanical Components EQ08 System Control Switch TestFunctional Component Definitions Electrical ComponentsTest Components TestingThermostat Adjustment Thermostat Bulb LocationDefrost Thermostat Heat Pump Models Only Resistor Heat Anticipator See FigureDefrost Bulb Location Heat Pump Models Capacitor Connections CapacitorsCapacitor Check with Capacitor Analyzer FAN MotorHeating Element Heat Pump Models Testing the Heating Element Electric Shock HazardHeating Element See Figure Drain PAN ValveOperating Sequence / Characteristics and Features Smart FANRefrigeration Sequence of Operation Equipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsFreeze Hazard Undercharged Refrigerant Systems Overcharged Refrigerant SystemsRestricted Refrigerant System Check Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the Coil Checking the Reversing ValveTouch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveExplosion Hazard Compressor Checks Ground Test Single Phase Resistance TestChecking Compressor Efficiency Recommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Rotary Compressor Special Troubleshooting and Service Blower Wheel / Housing / Condenser FAN / Shroud Routine MaintenanceCoils and Base PAN Excessive Weight Hazard AIR FilterSleeve / Drain Front CoverCooling only Room AIR Conditioners Troubleshooting Tips Problem Possible Cause ActionReplace fuse, reset breaker. If repeats, check Fused separately Problem Possible Cause Action Heat / Cool only Room AIR Conditioners Troubleshooting Tips Heat / Cool Room AIR Conditioners Trouble Shooting Tips Problem Possible Cause ActionHeat Pump System Cools When Heating is DesiredYES Normal Function of Valve Malfunction of ValveElectronic Control Cool only Models Electronic Control Cool only Models Electromechanical Control Cool only Models SL28L30-D,-E SL36L30A-D,A-E Page Electromechanical Control Cool with Electric Heat Models EL36L35A-D,A-E Electromechanical Control Heat Pump only Models YS13L33-D,-E YM18L34-D,-E YL24L35-E,-F Aham PUB. NO. RAC-1 Heat Gain from Quantity Factors Cooling Load Estimate FormDAY Following is an example using the heat load form Heat Load FormWindows & Doors Area, sq. ft Infiltration Windows & Doors AVGRoom AIR Conditioners Limited Warranty Page Technical Support Contact Information Friedrich AIR Conditioning CO
Related manuals
Manual 60 pages 54.38 Kb Manual 60 pages 45.7 Kb

2009, 2008 specifications

Friedrich 2008 and 2009 represent significant advancements in heating and cooling technology, particularly in the realm of air conditioning systems. Friedrich is known for producing robust and efficient HVAC solutions tailored for both residential and commercial applications. These models are particularly noteworthy for their innovative features and energy-efficient technologies that enhance user comfort and lower operational costs.

One of the main characteristics of the Friedrich 2008 and 2009 models is their emphasis on energy efficiency. Both units are designed to meet or exceed Energy Star standards, which indicates that they use less energy compared to standard models, contributing to greener living solutions. The incorporation of efficient compressors and high SEER (Seasonal Energy Efficiency Ratio) ratings ensures that users save money on their electricity bills while enjoying optimal cooling performance.

The units also feature advanced inverter technology, which allows for variable speed operation. This means that the system can adjust its cooling capacity based on the current temperature needs, resulting in more consistent comfort while reducing wear and tear on the equipment. Additionally, the inverter technology operates more quietly compared to traditional systems, making these models suitable for both home environments and commercial settings.

Friedrich 2008 and 2009 also provide users with enhanced control options. The inclusion of smart technology and Wi-Fi connectivity allows for remote monitoring and temperature adjustments via smartphones or tablets. Users can create schedules, set temperature preferences, and receive maintenance alerts, contributing to a more user-friendly experience.

Moreover, these models are designed with robust construction, featuring durable materials that withstand various weather conditions. Their compact footprint and sleek design make them suitable for window installation, while an array of sizes accommodates spaces of different dimensions.

Additionally, the air filtration systems in Friedrich 2008 and 2009 units improve indoor air quality. They effectively capture dust, allergens, and other particulates, ensuring a healthier environment for occupants.

In summary, Friedrich 2008 and 2009 models stand out for their energy efficiency, innovative inverter technology, smart controls, and robust construction. With a focus on user comfort and environmental responsibility, these models provide reliable solutions for effective heating and cooling in diverse applications.