Section 3: Configuration
SWITCH BANK 2 (SW2)
Audible Alarm
Switch 1 |
|
|
|
|
cUP | Audible signals enabled |
| ||
DOWN | Audible signals disabled |
| ||
Switch 2 Not Used |
|
| Rating(Amps) | CurrentDraw |
AC service rating |
| |||
|
|
| ||
| Switch 3 | Switch | Breaker | MaxAC |
|
|
| ||
|
| 4 |
|
|
| cUP | cUP | 10 A | 8 A |
| DOWN | UP | 15 A | 12A |
| UP | DOWN | 20 A | 16A |
| DOWN | DOWN | 30 A | 24A |
Maximum DC
Charging Amps
PS 2.5 |
| PS 3.0 |
|
12V | 24V | 12V | 24V |
55 | 30 | 55 | 30 |
90 | 45 | 90 | 45 |
100 | 55 | 100 | 60 |
100 | 55 | 120 | 60 |
Battery Size
Switch 5, 6, 7, 8 |
|
|
| Max DC charging current (amps) | ||||
|
|
|
| Battery | Prosine 2.5 | Prosine 3.0 | ||
#5 | #6 | #7 | #8 | Capacity | 12V | 24V | 12V | 24V |
|
|
|
|
|
|
|
|
|
cUP | cUP | cUP | cUP | 50 Ah | 11A | 11A | 11A | 11A |
DOWN | UP | UP | UP | 75 Ah | 25A | 25A | 25A | 25A |
|
|
|
|
|
|
|
|
|
UP | DOWN | UP | UP | 100 Ah | 33A | 33A | 33A | 33A |
DOWN | DOWN | UP | UP | 150 Ah | 50A | 50A | 50A | 50A |
|
|
|
|
|
|
|
|
|
UP | UP | DOWN | UP | 200Ah | 67A | 50A | 67A | 60A |
DOWN | UP | DOWN | UP | 300 Ah | 100A | 50A | 100A | 60A |
|
|
|
|
|
|
|
|
|
UP | DOWN | DOWN | UP | 400 Ah | 100A | 50A | 120A | 60A |
DOWN | DOWN | DOWN | UP | 500 Ah | 100A | 50A | 120A | 60A |
|
|
|
|
|
|
|
|
|
UP | UP | UP | DOWN | 600 Ah | 100A | 50A | 120A | 60A |
DOWN | UP | UP | DOWN | 700 Ah | 100A | 50A | 120A | 60A |
|
|
|
|
|
|
|
|
|
UP | DOWN | UP | DOWN | 800 Ah | 100A | 50A | 120A | 60A |
DOWN | DOWN | UP | DOWN | 1000 Ah | 100A | 50A | 120A | 60A |
|
|
|
|
|
|
|
|
|
UP | UP | DOWN | DOWN | 1200 Ah | 100A | 50A | 120A | 60A |
DOWN | UP | DOWN | DOWN | 1400 Ah | 100A | 50A | 120A | 60A |
|
|
|
|
|
|
|
|
|
UP | DOWN | DOWN | DOWN | 1700 Ah | 100A | 50A | 120A | 60A |
DOWN | DOWN | DOWN | DOWN | 2000 Ah | 100A | 50A | 120A | 60A |
|
|
|
| or greater |
|
|
|
|
Prosine 2.5/3.0 Installation & Operation Guide | 27 |