Section 7: Batteries
Cables
Inspect all battery cables for missing or damaged insulation or loose connections. Inspect any openings through which the cables pass. Ensure that all such openings are equipped with a rubber grommet or conduit to prevent chafing the cable. If necessary, replace worn grommets. If the cable insulation is worn, replace the cable.
Cabling & Hook-up Configurations
It is possible to connect individual batteries together to make a larger battery “bank” with heavy cables. The actual size of the cable depends upon whether the batteries are connected in parallel or series. Generally, the cables should not be smaller than the inverter
The best configuration is to connect the batteries both in series and
Connect several smaller batteries together when creating a battery bank of substantial size. There are three ways to do this. Batteries can be connected in parallel series or
Parallel Connection
Batteries are connected in parallel when all the positive terminals of a group of batteries are connected and then, separately, all the negative terminals are connected. In a parallel configuration, the battery bank has the same voltage as a single battery, but an amp/hour rating equal to the sum of the individual batteries.
12V
50 Ah
|
|
| 12V |
|
|
|
|
|
|
| 12V |
|
|
|
|
|
|
|
| 12V |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
| 50 Ah |
|
|
|
|
|
|
|
| 50 Ah |
|
|
|
|
|
|
|
|
| 50 Ah |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FUSED
DISCONNECT
12V INVERTER12V
(Total Battery Capacity
= 200 Amp Hours)