INSTALLATION
Battery Cable Fusing
A fuse is required by the NEC to protect the battery and cables. A UL Listed DC rated slow blow fuse must be installed in the positive
(+)battery cable, within 72 inches of the battery or within 7 inches of a positive bus or switch.
Recommended Fuse: UL Listed Class T JLLN with a DC Rating. This fuse with fuse holder is available from your dealer or Xantrex.
For Freedom 10 & 15
200 amp Fuse & Holder PN#
200 amp Fuse Only PN#
For Freedom 20, 25, & 30
300 amp Fuse & Holder PN#
300 amp Fuse Only PN#
*Compression / Ring Terminal ** Ring / Ring Terminal
HARDWARE STACK-UP OPTIONS
+ (red)
COMPRESSION / RING TERMINAL | EXPLODED VIEWS |
|
|
| |
NUT | OF FUSE ASSEMBLY |
|
LOCK WASHER | RING / RING TERMINAL | |
|
| FLAT WASHER |
|
INVERTER | BATTERY |
|
CABLE |
| |
CABLE |
| |
| INVERTER | |
| FUSE | |
| CABLE |
NUT
LOCK WASHER
FLAT WASHER
BATTERY
CABLE
FUSE HOLDER
WARNING
Improper stack up of hardware will cause excessive heat and fuse failure. Stack up as shown.
FUSE
FUSE HOLDER
28