INSTALLATION CHECKS
•Testing for backfeed. If a backfeed condition is indicated, disconnect from shorepower and disconnect the AC output wires from the inverter. Make sure the inverter is OFF.
Caution: Apply shorepower and measure for voltage between the black and white wires that were attached to the inverter output feeding the electrical panel or loads, not the inverter output wires. If there is voltage on these wires, a backfeed condition exists and must be corrected or damage will result.
3.Test the battery charger function:
•With shorepower applied and the
transfer switch engaged, the battery charger should be in operation. The CHARGE LED will blink for 8 seconds. After the 8 seconds, the unit will enter the charge mode and the LED will be illuminated. (When using Temperature Sensitive Charging, this time may be longer.)
When AC is available, the unit will auto- matically default to charge mode without the operator setting the unit in CHARGE mode. It is necessary to press the CHARGE switch OFF, if you do not want to charge.
Verify the charger is working by using a volt meter. Use this same method on the start or auxiliary battery connected to the echo- charge to verify
If using a Remote Control Panel, DC Amps LED indicates charger output and the DC Volts LED indicates an increase in battery voltage.
Note: The house battery bank must be above 13.0 volts for the
•Turn the inverter
Repeat the test for transfer and battery charger with the generator if you have one.
Congratulations, you have completed a successful installation.
Note: For low power system shutdown mode, both the INVERT and CHARGE LEDs must be OFF.