Studer Innotec HPC5048, HPC2512, HPC7048 Connection to the 230Vac-consumer appliances AC Output

Page 11

STUDER INNOTEC

HP-COMPACT

riously damage the HP-COMPACT. For instance the connection of a 24 V battery with the HP-COMPACT 2512.

If by mistake the HP-COMPACT has been wrongly been connected (reverse battery polar- ity) it is likely that the internal protection fuse has melted and has to be replaced. In that case it is necessary to disconnect all connections to the HP-COMPACT, including the bat- tery. If after the fuse replacement and after re-connection of the battery with the right polar- ity, the HP-COMPACT remains out of order, it must be brought back to your merchant for service.

3.6.2 Connection to the 230Vac-consumer appliances (AC OUTPUT)

The 230V consumer appliances must be connected to the terminals AC OUTPUT with ca- bles which cross section has to follow the local rules in force (usually 2,5mm2). Connec- tions are marked as follows “N“ Neutral, “PE“ Earth (connected to the appliance box), “L“ Live.

Caution: High voltages can be there. Make sure that the HP-COMPACT is turned off (LED 13 lighting) before the connection.

3.6.3 Connection to the 230Vac Input (AC INPUT)

The 230V-supply from network or from a generator must be connected to the input termi- nals AC INPUT with cables which cross section depends on the power source (usually 2,5mm2). Connections are marked as follows: “N“ Neutral, “PE“ Earth, “L“ Live (connected to the appliance case).

3.6.4 Connection to Auxiliary Contact

This contact is a potential free change over contact The currents and voltages allowed for this contact are max. 16A/250Vac. The LED 5 “Contact active” shows the position of them: alight mind active and off mind non-active. The schematic view of the connections on the front, show the relay in the non-active mode.

3.6.5 Connection to Remote control

The Remote Control RCC-01 is connected in the terminal marked „Remote control“ with a 20m long cable and a RJ11/8 connector. The Remote Control can be plugged IN or plugged OUT during any operation situation. Push in the connector softly until you hear the „click“ showing that the connector is locked. The same applies to the plug in the Remote Control.

The length of the cable for Remote Control should not exceed 40m. We deliver it with 20m cable.

3.6.6Connection to Temperature Sensor (Temp.)

The temperature sensor CT-35 is connected in the terminal marked „Temp“ with a 3m long cable and a RJ11/6 connector. The temperature sensor can be plugged IN or plugged OUT during any operating situation. Push in the connector softly until you hear the „click“ showing that the connector is locked. The temperature sensor must be glued to the wall of the battery or near it. The Temperature Sensor cable must not be tied together with the battery cables or laid in a rope/bundle.

3.6.7 Connection to the Remote Control for the „Power Sharing“ (RPS-01)

This remote control is connected with a 20m long cable and a RJ11/6 connector in the connection terminal „F“ (Temp. sensor). It can be connected and disconnected at any time. Push in the connector softly until you hear the „click“ showing that the connector is locked. In case the remote control is connected together with the Temp. sensor, a short cable with a Y-connector will be connected in the terminal „F“ (can be supply as an option).

User manual

HP-COMPACT V3.0 E

11

Image 11
Contents User and installer Manual Summary Operating instructions Quality and WarrantyWarranty Disclaimer General InformationSpecial precautions PrecautionsIntroduction Battery connecting Battery chargerRemote control Remote control for Power SharingConnection in parallel and in serie Mounting and installingInstallation place Connection in serieProtection cover of the terminals connections General instructions on connectingFixing ConnectionsCabling BatteryConnection to battery Pre-installation settingsConnection to the 230Vac Input AC Input Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac-consumer appliances AC OutputDisplay and control parameters ControlCharger Inverter Inverter Push buttonsTurning Knobs Overheating Over Temp Battery ConditionCharge detection system „Standby OverloadEqualization charging Cycle of chargeCharging current Input current repartition Power sharingSet the transfer voltage threshold Transfer systemMultifunctional Contact Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Temperature sensor Remote ControlTable of voltage and timing threshold Battery voltageProgramming Auxiliary contactPrinciple Set the voltage and timing thresholdExample start of a genset with the HP-COMPACT Disabling some of the HP-COMPACT functions Power cut of the second priority loadsDiagram of the different modes Manual operating of Auxiliary ContactEC Compliance Installation MaintenanceHPC2512 HPC4024 HPC5048 HPC7048 Technical Data