Studer Innotec HPC4024, HPC2512, HPC7048, HPC5048 Example start of a genset with the HP-COMPACT

Page 22

STUDER INNOTEC

HP-COMPACT

COMPACT which is indicated with a LED. The programming is possible for one or more operating situations. If the contact is programmed for many situations, it is activated as soon as the HP-COMPACT finds itself in any one of the programmed situations. That means that the work of the contact meets that of the logic OR–Function.

5.4.2 The programming of the Auxiliary Contact is carried out in the following Steps

The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4 „Program“ is lit as an indication, that the HP-COMPACT is in program mode.

A blinking LED shows the programmed condition for the auxiliary contact (LED 10/11/ 12/13 factory setting).

With the Push Button 20 (select), select the desired condition in which the contact should be activated.

With the Push Button 19 (Change status) confirm or change the status for this condition.

If desired, with the Push Button 20 (select) select another condition in which the contact should be activated.

With the Push Button 19 (Change status) confirm or change the status for this condition.

If during 20 seconds no buttons are pushed, then the settled values are automatically stored and the HP-COMPACT switches back to normal operating condition.

5.4.3Auxiliary Contact as generator starter As per the battery capacity

When in the programming of the Auxiliary Contact, the Battery Capacity (LED 15-18) is used as a condition, you must then take note of the following requirements.

If you have to start an emergency back-up supply with a battery having a certain residual capacity, then two battery levels must be programmed. The first (i.e. Battery 25% LED 17) for the starting or activating the Auxiliary Contact and the second (i.e. Battery 100% LED15) for stopping or disabling the Auxiliary Contact. Programmed like this the Auxiliary Contact works with the lowest set condition and stops when it has reached the highest programmed condition through charging.

Example: start of a genset with the HP-COMPACT

In order to program the auxiliary contact to start at 25% and to stop at 75% of the battery state-of-charge, here is the procedure to follow:

-Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then the states will be displaid blinking (factory settings LED’s 10/11/12/13). As these states are not wished for the start of the genset, they must be disabled.

-With the key (select) 20, select the LED’s to disable (the active LED’s are blinking) and disable them with the key 19 Change Status. Select the other LED’s to switch off with the key (select) 20 and switch them off with the key 19 Change Status until all are disabled.

-Then select the LED 17 with the key (select) 20 and activate the contact with the key 19 Change Status. The genset will start once the LED 17 switches of.

-Then select the LED 16 with the key (select) 20 and activate the contact with the key 19 Change Status. The genset will stop once the LED 16 switches on.

-If no key is activated during 30 seconds, the normal operation states are displaid automatically again.

For a control the key Program can be pressed at least 2 seconds. The values set are dis- plaid blinking.

User manual

HP-COMPACT V3.0 E

22

Image 22
Contents User and installer Manual Summary General Information Quality and WarrantyWarranty Disclaimer Operating instructionsPrecautions Special precautionsIntroduction Remote control for Power Sharing Battery chargerRemote control Battery connectingConnection in serie Mounting and installingInstallation place Connection in parallel and in serieConnections General instructions on connectingFixing Protection cover of the terminals connectionsBattery CablingPre-installation settings Connection to batteryConnection to the 230Vac-consumer appliances AC Output Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac Input AC InputCharger Inverter ControlDisplay and control parameters Turning Knobs Push buttonsInverter Overload Battery ConditionCharge detection system „Standby Overheating Over TempCycle of charge Equalization chargingInput current repartition Power sharing Charging currentTransfer system Set the transfer voltage thresholdDelayed mode of the Transfer System Fast UPS- Mode for the Transfer SwitchMultifunctional Contact Remote Control Temperature sensorAuxiliary contact Battery voltageProgramming Table of voltage and timing thresholdSet the voltage and timing threshold PrincipleExample start of a genset with the HP-COMPACT Manual operating of Auxiliary Contact Power cut of the second priority loadsDiagram of the different modes Disabling some of the HP-COMPACT functionsInstallation Maintenance EC ComplianceTechnical Data HPC2512 HPC4024 HPC5048 HPC7048