COMPACT which is indicated with a LED. The programming is possible for one or more operating situations. If the contact is programmed for many situations, it is activated as soon as the
5.4.2 The programming of the Auxiliary Contact is carried out in the following Steps
The Push Button 21 (Program) presses down for min. 2 seconds. The LED 4 „Program“ is lit as an indication, that the
A blinking LED shows the programmed condition for the auxiliary contact (LED 10/11/ 12/13 factory setting).
With the Push Button 20 (select), select the desired condition in which the contact should be activated.
With the Push Button 19 (Change status) confirm or change the status for this condition.
If desired, with the Push Button 20 (select) select another condition in which the contact should be activated.
With the Push Button 19 (Change status) confirm or change the status for this condition.
If during 20 seconds no buttons are pushed, then the settled values are automatically stored and the
5.4.3Auxiliary Contact as generator starter As per the battery capacity
When in the programming of the Auxiliary Contact, the Battery Capacity (LED
If you have to start an emergency
Example: start of a genset with the HP-COMPACT
In order to program the auxiliary contact to start at 25% and to stop at 75% of the battery
-Press the key AUX. CONTACT (Program) 21 during at least 2 seconds. Then the states will be displaid blinking (factory settings LED’s 10/11/12/13). As these states are not wished for the start of the genset, they must be disabled.
-With the key (select) 20, select the LED’s to disable (the active LED’s are blinking) and disable them with the key 19 Change Status. Select the other LED’s to switch off with the key (select) 20 and switch them off with the key 19 Change Status until all are disabled.
-Then select the LED 17 with the key (select) 20 and activate the contact with the key 19 Change Status. The genset will start once the LED 17 switches of.
-Then select the LED 16 with the key (select) 20 and activate the contact with the key 19 Change Status. The genset will stop once the LED 16 switches on.
-If no key is activated during 30 seconds, the normal operation states are displaid automatically again.
For a control the key Program can be pressed at least 2 seconds. The values set are dis- plaid blinking.