Studer Innotec user manual Technical Data, HPC2512 HPC4024 HPC5048 HPC7048

Page 25

STUDER INNOTEC

HP-COMPACT

8 Technical Data

 

Model

HPC2512

 

HPC4024

 

HPC5048

 

HPC7048

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal battery voltage

12 V

 

24 V

 

 

48 V

 

48 V

 

 

Input voltage range

9.5 – 17 V

 

19 – 34 V

 

 

38 – 68 V

 

38 – 68 V

 

Nominal power @ 25°C

2500 W

 

4000 W

 

 

5000 W

 

7000 W

 

Maximum load 30 min. @ 25°C

2800 W

 

4500 W

 

 

6000 W

 

8000 W

 

Maximum load 5 sec

 

 

 

3 x

Pnom

 

 

 

 

Maximum load

 

 

 

up to short circuit

 

 

 

Maximum asymmetric load

 

 

 

up to Pnom

 

 

 

Standby adjustment

 

 

 

1 to 25 W

 

 

 

Cos ϕ

 

 

0.1 - 1

 

 

 

 

 

Maximum efficiency

93 %

 

 

94 %

 

96 %

 

96 %

 

 

Consumption OFF/Standby/ON

1.4/1.8/10 W

 

1.7/2/16 W

 

 

2/2.5/18 W

 

2/3/25 W

 

Output voltage

 

 

 

230 Vac

 

(0 / - 10%)

 

 

 

 

Output frequency crystal controlled

 

 

 

50 Hz

± 0.05 %

 

 

 

 

Total harmonic distortion

 

 

< 2%

 

 

 

 

 

Dynamic behaviour on load change 0 100 %

 

 

 

0.5 ms

 

 

 

Overload and short circuit protection

 

 

Automatic disconnection with 3 time restart attempt

 

 

 

Overheat protection

 

Acoustic warning before shut-off - with automatic restart

 

Battery charger (4 STEP) I-U-Uo-Equalize (every 25 cycles)

 

 

 

 

 

 

 

 

 

Charging current adjustable

0 – 110 A

 

0 – 100 A

 

 

0 – 70 A

 

0 – 90 A

 

Input current balance adjustment (Power Sharing)

1 – 30 A

 

1 – 30 A

 

 

1 – 30 A

 

1 – 50 A

 

Maximum input voltage

 

 

 

265

Vac

 

 

 

 

Minimum input voltage

 

 

 

Adjustable threshold from 150 to 230 Vac

 

 

 

Input frequency

 

 

 

45 – 65 Hz

 

 

 

Power Factor Correction (PFC)

 

 

 

EN 61000-3-2

 

 

 

Battery control (thresholds and times adjustable by the user)

 

 

 

 

 

 

 

 

 

Absorption time

 

 

 

 

0-4h

 

 

 

End charge cycle voltage

14.4 V

 

28.8 V

 

 

57.6 V

 

57.6 V

 

Floating voltage

13.6 V

 

27.2 V

 

 

54.4 V

 

54.4 V

 

Equalisation voltage

15.6 V

 

31.2 V

 

 

62.4 V

 

62.4 V

 

Deep-discharge protection

10.8 V

 

21.6 V

 

 

43.2 V

 

43.2 V

 

Temperature compensation (option CT-35)

 

 

 

-3mV / °C /

cell

 

 

 

 

General data

 

 

 

 

 

 

 

 

 

 

 

Multifunction contact - potential free (3 points)

 

 

 

16 A – 250 Vac

 

 

 

Max. current on transfer relay

30 A / 6.9 kVA

 

30 A / 6.9 kVA

 

 

30 A / 6.9 kVA

 

50 A / 11.5 kVA

 

Transfer time

 

 

 

< 20 ms

 

 

 

 

 

Weight

33 kg

 

39 kg

 

 

41 kg

 

48 kg

 

Dimension h x l x L [mm]

242/288/480

 

242/288/480

 

242/288/480

 

242/288/500

 

IP protection index

 

 

 

IP 20

 

 

 

 

 

EEC conformity

EN50081 I/II, EN 55014 – EN 55022, EN 61000-3-2

 

 

 

IEC 801 I/II/III/IV, CEI 555, IEC 1000-3-2, LVD 73/23/EEC

 

 

 

 

 

 

 

Working range

-20 to 55°C

 

 

 

 

 

 

 

 

 

Ventilation

from 45°C

 

 

 

 

 

 

 

 

 

Acoustic level without / with ventilation

< 10 dB / < 35 dB

 

 

 

 

 

 

 

 

 

Recommended battery capacity (C10)

> 5 x Pnom/Unom

 

 

 

 

 

 

 

 

 

Warranty

2 years

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

Remote control (112 x138 x 25mm / 20 m cable)

RCC-01

 

 

 

 

 

 

 

 

 

 

Remote power sharing (20 m. cable)

RPS-01

 

 

 

 

 

 

 

 

 

 

Battery temp. sensor (58 x 51.5x 22mm / 3 m cable)

CT-35

 

 

 

 

 

 

 

 

 

Data may change without any notice

User manual

HP-COMPACT V3.0 E

25

Image 25
Contents User and installer Manual Summary Warranty Disclaimer Quality and WarrantyGeneral Information Operating instructionsSpecial precautions PrecautionsIntroduction Remote control Battery chargerRemote control for Power Sharing Battery connectingInstallation place Mounting and installingConnection in serie Connection in parallel and in serieFixing General instructions on connectingConnections Protection cover of the terminals connectionsCabling BatteryConnection to battery Pre-installation settingsConnection to Temperature Sensor Temp Connection to Remote controlConnection to the 230Vac-consumer appliances AC Output Connection to the 230Vac Input AC InputCharger Inverter ControlDisplay and control parameters Turning Knobs Push buttonsInverter Charge detection system „Standby Battery ConditionOverload Overheating Over TempEqualization charging Cycle of chargeCharging current Input current repartition Power sharingSet the transfer voltage threshold Transfer systemDelayed mode of the Transfer System Fast UPS- Mode for the Transfer SwitchMultifunctional Contact Temperature sensor Remote ControlProgramming Battery voltageAuxiliary contact Table of voltage and timing thresholdPrinciple Set the voltage and timing thresholdExample start of a genset with the HP-COMPACT Diagram of the different modes Power cut of the second priority loadsManual operating of Auxiliary Contact Disabling some of the HP-COMPACT functionsEC Compliance Installation MaintenanceHPC2512 HPC4024 HPC5048 HPC7048 Technical Data