Studer Innotec HPC4024, HPC2512 Charge detection system „Standby, Overload, Overheating Over Temp

Page 14

STUDER INNOTEC

HP-COMPACT

The Inverter mode is displayed through LED 9 (Inverter). If the Inverter Mode is disabled (see chap. 5.5) LED 9 will blink. If the LED 9 is lit, the Inverter is in operation and you have 230Vac at the output AC OUT. The actual power of the connected appliance is displayed on the power monitor 25 and on the Remote Control.

4.5.1 Charge detection system „Standby“

In order to avoid unnecessary discharge of the battery, the inverter switches OFF auto- matically if no appliance is connected and switches ON automatically again if appliance is connected. The LED 8 blinks if the inverter is in Standby-Mode. The switching-on/starting level can be adjusted with the turning knob 24 „STANDBY”. Adjusting the switching-on level is as follows: Switch off all consuming devices, turn the Turning Knob 24 to the right until the LED 8 is blinking, switch on the smallest consuming device (i.e. Mobile phone charger), turn the Turning Knob slowly to the left until LED 8 is lit.

If the Standby-Mode is not wanted, turn the Turning Knob 24 to the left, to the OFF posi- tion.

4.5.2Overload

If the Inverter is too long or too heavily overloaded, it switches off. The LED 11 „Overload“ is lit and LED 13 „OFF“ blinks. After ca. 10 seconds the Inverter switches on automatically. If the Inverter is overloaded four times one after another in a short time, then it no longer switches on automatically. The LED 13 remains lit. Press the push button 19 „ON/OFF“ in order to switch on the Inverter.

4.5.3 Overheating (Over Temp.)

If the Inverter has been overloaded for a long time or it has been working in too high sur- rounding temperatures, it will switch off. The LED 10 „Over Temp.“ is lit and the LED 13 „OFF“ blinks. After cooling down, the inverter switches back on automatically. One minute before the inverter switches off for too high temperature it gives out an acoustic alarm sig- nal. If the Auxiliary Contact has been programmed to detect the high temperature then it synchronizes the relay with the alarm signal. In this way, for example, an emergency back- up system can be started without any break in the energy supply.

4.5.4 Battery Condition

Deep discharge of the lead-acid batteries leads to high losses in capacity and early aging. That is why the battery condition is continuously controlled and supervised. With low volt- age the inverter switches off. The LED 12 „L/H Batt.“ is lit and the LED 13 „OFF“ blinks. When the battery voltage gets up to 12.1V / 24.2V / 48.4V, the Inverter switches on auto- matically. One minute before the Inverter switches off due to low voltage it gives out an acoustic alarm signal. If the Auxiliary Contact has been programmed to detect the low voltage then it synchronizes the Aux. Contact with the alarm signal. In this way, for exam- ple, an emergency back up system can be started without any break in the energy supply. The low voltage is set to 11.8V / 23.6V / 47.2V. These settings are standard for most bat- teries. These voltage levels are maintained by the built-in Battery-Management-System of the HP-COMPACT by matching the load and the battery condition.

This setting is comparable with the levels of 10.8V/ 21.6V / 43.2 which are given for most batteries at nominal load.

All voltage levels can be programmed. See the instructions under the section on Pro- gramming. Check with your battery supplier which voltage values should be set.

User manual

HP-COMPACT V3.0 E

14

Image 14
Contents User and installer Manual Summary General Information Quality and WarrantyWarranty Disclaimer Operating instructionsPrecautions Special precautionsIntroduction Remote control for Power Sharing Battery chargerRemote control Battery connectingConnection in serie Mounting and installingInstallation place Connection in parallel and in serieConnections General instructions on connectingFixing Protection cover of the terminals connectionsBattery CablingPre-installation settings Connection to batteryConnection to the 230Vac-consumer appliances AC Output Connection to Remote controlConnection to Temperature Sensor Temp Connection to the 230Vac Input AC InputDisplay and control parameters ControlCharger Inverter Inverter Push buttonsTurning Knobs Overload Battery ConditionCharge detection system „Standby Overheating Over TempCycle of charge Equalization chargingInput current repartition Power sharing Charging currentTransfer system Set the transfer voltage thresholdMultifunctional Contact Fast UPS- Mode for the Transfer SwitchDelayed mode of the Transfer System Remote Control Temperature sensorAuxiliary contact Battery voltageProgramming Table of voltage and timing thresholdSet the voltage and timing threshold PrincipleExample start of a genset with the HP-COMPACT Manual operating of Auxiliary Contact Power cut of the second priority loadsDiagram of the different modes Disabling some of the HP-COMPACT functionsInstallation Maintenance EC ComplianceTechnical Data HPC2512 HPC4024 HPC5048 HPC7048