Error Log

Section 9-3

Time Information

The time is recorded in BCD with one byte each for the year (the rightmost two digits), month, day, hour, seconds, and minutes of the time the error occurred.

Note 1. The PLC’s time information can be read and used in the Controller Link Unit. When the time cannot be read from the PLC, all error log times will but 0. This can occur for PLC startup errors, Unit No. errors, CPU Unit er- rors, or PLC model errors. When error logs like these are read from the Controller Link Support Software, they will be dated 0 s, 0 min, 0 hr, 0 day, 0 month, 2000.

2.When replacing the battery for CS/CJ-series PLCs, it will be necessary to switch the power supply ON and reset the internal clock.

If the internal clock is not reset, time information in the error log will not be recorded correctly.

3.The time information will be all zeros for CQM1H-series PLCs unless a Memory Cassette with a clock is mounted in the CPU Unit. The time infor- mation will be all zeros in the year 2000 if it is read from Support Software.

9-3-2

Error Codes

 

 

 

 

 

 

The following table lists the error codes (in 4-digit hexadecimal) and the con-

 

tents of the errors.

 

 

 

 

 

 

 

 

 

 

 

Error

Contents

Detail code

Correction

Written to

Applicable

code

 

 

 

 

EEPROM

PLC

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

 

0001

PLC watchdog timer error

00 Hex

00 Hex

Replace PLC’s CPU

Yes

All

Hex

 

 

 

Unit.

 

 

 

 

 

 

 

 

 

0002

PLC service monitor error

Monitor time (unit: ms)

Check operating

Yes

CV, CS/CJ

Hex

 

 

 

environment.

 

 

 

 

 

 

 

 

 

0003

PLC shared RAM error

01 Hex:

00 Hex

Check operating

Yes

CV

Hex

 

Cyclic

 

environment.

 

 

 

 

02 Hex:

 

 

 

 

 

 

Event

 

 

 

 

 

 

04 Hex:

 

 

 

 

 

 

CPU bus link

 

 

 

 

 

 

 

 

 

 

 

0004

CPU Bus Unit ID number error

00 Hex

00 Hex

Check I/O

Yes

CV, CS/CJ

Hex

 

 

 

Connecting Cables.

 

 

 

 

 

 

 

 

 

0005

Unit number error

Unit set

The value

Check the Unit

Yes

CV

Hex

 

value

recognized

number setting. Rec-

 

 

 

 

 

by the CPU

reate the I/O table.

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

0006

CPU Unit error

Bit 11:No relevant Unit in

Check the Unit num-

Yes

CV, CS/CJ

Hex

 

I/O table.

ber settings. Recre-

 

 

 

 

Bit 12: Hardware test unit

ate the I/O table.

 

 

 

 

 

 

 

 

 

number recognized.

 

 

 

 

 

Bit 13: Incorrect unit num-

 

 

 

 

 

ber.

 

 

 

 

 

 

Bit 14: Duplicated unit

 

 

 

 

 

number.

 

 

 

 

 

 

 

 

 

 

000D

PLC model error

Not set

 

Refer to 1-2-4 Con-

Yes

C200HX/HG/

Hex

 

 

 

troller Link Unit Mod-

 

HE

 

 

 

 

els and PLCs and

 

 

 

 

 

 

PLCs and check the

 

 

 

 

 

 

PLC model.

 

 

 

 

 

 

 

 

 

314