Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21 CVM1 or CV-series Startup Node

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 170
Image 170

Setting Data Links

Section 5-2

CVM1 or CV-series Startup Node

Set the following DM Parameter Area of the PLC of the startup node.

N: DM 2000 + 100 (Unit number of Controller Link Unit)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Word N

0

0

0

0

0

0

0

0

 

 

 

 

0

0

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Always 0.

 

 

 

 

 

 

 

 

Data link mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– : Other settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set to 01 for automatic setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(00 is for manual setting. Other values are invalid.)

15

8

7

0

N+1 Area 1 data link start word (BCD)

N+2 Area 1 type

N+3 Number of send words per node of area 1 (BCD)

N+4 Rightmost 4 digits of data link start word of area 2 (BCD)

 

 

Leftmost digit of data link start word

N+5 Area 2 type

of area 2 (BCD)

N+6 Number of send words per node of area 2 (BCD)

N+7 First data link status word (BCD)

 

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

N+8

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

N+9

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

BCD: Set the value as binary-coded decimal.

Nodes to participate in the data links

The numbers indicate node numbers. The value assigned indicates whether the node is to participate in the data links.

Participate: 1

Not participate: 0

Settings

Item

 

Setting range

 

 

Data link mode

Specify automatic (01).

 

 

Area 1 data link start

Set the word address in BCD.

word

CIO Area: CIO 0000 to CIO 2555

 

 

LR Area: LR 000 to LR 199 (*)

 

*: When a word between LR 000 and LR 199 is speci-

 

fied, the data link area will be allocated between CIO

 

1000 and CIO 1199.

 

 

Area 1 type

Set the area for area 1 in BCD.

 

CIO Area:

80

 

LR Area:

86

 

Area 1 not used: 00

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

words) for node of area 1

The total number of send words of area 1 and area 2

 

must not exceed 1,000.

 

When area 1 is not used, set to 0.

 

 

Area 2 data link start

Set the word address in BCD.

word

DM Area: DM 0000 to DM 8191

 

 

 

(CV500/CVM1-CPU01)

 

 

DM 0000 to DM 24575 (Other CPU Units)

 

EM Area: Banks 00 to 07, EM 0000 to EM 32765

 

 

(EM must be installed)

 

 

Area 2 type

Set the area for area 2 in BCD.

 

DM Area:

82

 

EM Area: Banks 00 to 07: 90 to 97

 

Area 2 not used: 00

 

 

 

147

Page 170