Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21 Area Range CV500, CVM1-CPU01, CVM1-CPU11/21

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 208
Image 208

Introduction

Section 6-1

C200HX/HG/HE PLCs

 

 

Area

Range

 

 

 

 

Internal Relay Area 1

IR 000 to IR 235 (See note 1.)

 

 

 

 

Special Relay Area 1

SR 236 to SR 255 (See note 1.)

 

 

 

 

Special Relay Area 2

SR 256 to SR 299 (See note 1.)

 

 

 

 

Internal Relay Area 2

IR 300 to IR 511 (See note 1.)

 

 

 

 

Link Relay

LR 00 to LR 63

 

 

 

 

Holding Relay

HR 00 to HR 99

 

 

 

 

Timer/Counter

T/C 000 to T/C 511

 

 

 

 

Auxiliary Relay

AR 00 to AR 27

 

 

 

 

DM Area

DM 0000 to DM 6655

 

 

 

 

Extended DM Area

EM 0000 to EM 6143 (See note 2.)

 

 

 

Note 1. Words in the Internal Relay Area 1 (IR 000 to IR 235) and Special Relay Area 1 (SR 236 to SR 255) are continuous in memory, and any range of words within these areas can be transferred in a single operation. The same is true for Special Relay Area 2 (SR 256 to SR 299) and Internal Re- lay Area 2 (IR 300 to IR 511). You cannot, however, transfer data in a range that crosses the boundary between Special Relay Area 1 (SR 236 to SR 255) and Special Relay Area 2 (SR 256 to SR 299).

SR 253 to SR 255 cannot be written at the source node, even if they are specified by the RECV instruction’s beginning receive word at the source node.

2.For details on extended DM Area and the number of banks, refer to the op- eration manual for the PLC model that is being used.

CVM1 and CV-series PLCs

Area

Range

 

 

 

 

CV500, CVM1-CPU01

 

CV1000/2000,

 

 

 

CVM1-CPU11/21

 

 

 

 

CIO Area

CIO 0000 to CIO 2555

 

 

 

 

CPU Bus Link Area

G000 to G255 (See note 1.)

 

 

 

 

Auxiliary Area

A000 to A511 (See note 2.)

 

 

 

 

Timer Area

T000 to T511

 

T000 T1023

 

 

 

 

Counter Area

C000 to C511

 

C000 to C1023

 

 

 

 

DM Area

DM0000 to DM8191

 

DM0000 to DM24575

 

 

 

 

Expansion DM Area

---

 

EM00000 to EM32765 (See

 

 

 

note 3.)

Note 1. Writing is not possible to words G000 through G007 in the CPU Bus Link Area.

2.Writing is not possible to words A256 through A511 in the Auxiliary Area.

3.Expansion DM can be used by mounting an Expansion DM Unit to a CV1000/2000 or CVM1-CPU11/21 PLC. A maximum of eight banks can be used, depending on the type of Expansion DM. For details, refer to the CVM1 and CV-series PLC operation manuals.

CQM1H-series PLCs

Area

Range

 

 

IR/SR Area

IR 000 to SR 255 (See note 1.)

 

 

LR Area

LR 00 to LR 63

 

 

HR Area

HR 00 to HR 99

 

 

Timer/Counter Area

TIM/CNT 000 to TIM/CNT 511

 

 

AR Area

AR 00 to AR 27

 

 

185

Page 208
Image 208
Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 Area Range CV500, CVM1-CPU01, CVM1-CPU11/21