Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 Error Log Table Configuration

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 336
Image 336

Error Log

Section 9-3

9-3 Error Log

The error log records errors that occur in the Controller Link Unit and the time they occur. The error log can be read or cleared by using Programming Devices, such as the Controller Link Support Software, the CX-Net, or Sup- port Software for the CPU Unit (SYSMAC Support Software), or by using the message service (FINS commands for the Controller Link Unit.)

9-3-1 Error Log Table

Errors are recorded in an error log table in the Unit’s RAM, with one record for each error and a maximum of 39 records.

Errors of significance are also recorded in the Unit’s EEPROM so that when the power to the Unit is turned OFF or reset, a record of the error will remain. (The error log table in EEPROM automatically reads the Unit’s RAM when the power is turned ON again.)

Item

Specification

 

 

No. of records

39 max.

 

 

Data code

Binary (Times are in BCD)

 

 

Length of each record

10 bytes

 

 

Configuration of records

Error code: 2 bytes (Refer to page 314)

 

Detail code: 2 bytes (Refer to page 314)

 

Time: 6 bytes (Refer to the following

 

page)

 

 

Record order

From the oldest record to the most

 

recent.

 

 

If the number of records exceeds 39, the oldest record will be deleted and the most recent error recorded.

Error Log Table Configuration

0

Error code

 

 

Detail

 

Min

S

Record

(Oldest)

 

 

Day

Hour

 

Year

Month

 

Error code

 

 

Detail

 

Min

S

Record

 

Day

Hour

 

Year

Month

 

Error code

 

 

Detail

 

Min

S

Record

(Newest)

 

 

Day

Hour

 

Year

Month

 

313

Page 336
Image 336