Unit Installation

Section 3-2

Installing with Another Communications Unit

When installing a Controller Link Unit along with another Communications

Unit, such as a SYSMAC LINK Unit or a SYSMAC NET LINK Unit mount both

Units in the 2 slots on the left of the CPU Unit.

CPU Backplane

Install the Controller Link Unit in one slot and the other Unit in the other slot.

CPU Unit

Other Communications Unit

C200HW-CLK21

Controller Link Unit

CPU Unit (C200HE-CPU32/42-(Z)E C200HG-CPU33/43/53/63-(Z)E C200HX-CPU34/44/54/64-(Z)E

C200HW-COM01/04

C200HW-CE002 Bus Connection UnitCommunications Board (For two Units)

Installing with a PC Card Unit

When installing a Controller Link Unit along with a PC Card Unit, mount the Controller Link Unit in the first slot on the left of the CPU Unit. Use the C200HW-CE012 Bus Connection Unit.

C200HW-PCU01

PC Card Unit

PC Card Unit

Controller Link Unit

CPU Unit

C200HW-CLK21

Controller Link Unit

CPU Unit (C200HE-CPU32/42-(Z)E C200HG-CPU33/43/53/63-(Z)E C200HX-CPU34/44/54/64-(Z)E

C200HW-CE012 Bus Connection Unit

CVM1 and CV-series PLCs

C200HW-COM01/04 Communications Board

Up to four Controller Link Units for CVM1 and CV-series PLCs can be installed in a CPU Backplane or a Expansion CPU Rack (including both Opti- cal and Wired Units). Controller Link Units cannot be installed on an Expan- sion I/O Rack, a SYSMAC BUS Slave Rack, or a SYSMAC BUS/2 Slave Rack.

The CVM1 and CV-series Controller Link Unit is classified as a CPU Bus Unit and must be mounted in a CPU bus slot.

Note Tighten the screws on the Backplane to a torque of 1.2 N • m. Tighten the fixed screws on the CPU Unit to a torque of 0.9 N • m.