Component Names and Functions

Section 3-1

3-1-5 CQM1H-series Controller Link Unit

Indicators (Refer to p. 53 and 276)

LED indicators that display the Unit and network status.

Node address switches (Refer to p. 101)

Two rotary switches. The node address of the Unit on the

Controller Link Network is set in 2-digit decimal.

Baud rate switch (Refer to p. 101)

bit/s

Terminating resistance switch (Refer to p. 102)

k

A slide switch. Use this switch to set the terminating resistance to ON for the nodes at both ends of the Controller Link Network.

Terminal block for the communications cable (Refer to p. 66)

Terminals to connect to the Controller Link Network communications cable (twisted-pair cable).

Wired Unit Indicators

Name

Color

Status

 

Meaning

 

 

 

 

RUN

Green

Lit

Unit operating normally.

(operating)

 

 

 

 

 

 

Not lit

Unit error.

 

 

 

 

 

 

 

 

 

 

TER

Yellow

Lit

Terminating resistance switch ON.

(terminating

 

 

 

 

 

 

Not lit

Terminating resistance switch OFF.

resistance)

 

 

 

 

 

 

ERC (communica-

Red

Lit

Communications error, node address

tions error)

 

 

setting error (same address set twice), or

 

 

 

hardware error.

 

 

 

 

 

 

 

 

Not lit

Normal operation

 

 

 

 

ERH

Red

Lit

PLC error, PLC interface error, or

(PLC error)

 

 

EEPROM error

 

 

 

 

 

 

 

 

 

 

Not lit

No error.

 

 

 

 

 

 

INS

Yellow

Lit

Unit is participating (inserted) in the net-

(network

 

 

work.

 

 

participation)

 

 

 

 

 

 

Not lit

Unit is not participating (inserted) in the

 

 

 

 

 

network.

 

 

 

 

 

 

 

 

M/A

Yellow

Lit

Manual

 

Note:

(data link mode)

 

 

(see note)

 

M/A is always not lit

 

 

 

 

 

when data links are not

 

 

Not lit

Automatic

 

 

 

 

active in the network.

 

 

 

 

 

 

 

 

 

 

LNK

Yellow

Lit

Participating in data links.

(data link)

 

 

 

 

 

 

Flashing

Error in data link tables.

 

 

 

 

 

 

 

 

Not lit

Not in a data link or data link inactive.

 

 

 

 

SD

Yellow

Lit

Data transmission.

(send)

 

 

 

 

 

 

Not lit

No data transmission.

 

 

 

 

 

 

 

 

RD

Yellow

Lit

Data reception.

 

 

(receive)

 

 

 

 

 

 

Not lit

No data reception.

 

 

 

 

 

 

 

 