Troubleshooting Error Messages in CX-Net Data Link Table Check

Section 9-4

 

 

 

 

Error message

Troubleshooting

 

 

 

 

Node XX Dest Over-

Warning: Overflow occurred

The number of receive words at the destination node is

flow

 

larger than the number of send words at the source node.

 

 

Change the number of send words or number of receive

 

 

words if the allocations are not intended. If the allocations

 

 

are intended, the data link tables can be transmitted without

 

 

making any changes.

 

 

 

 

 

Warning: Block outside bounds of

The number of receive words at the destination node is

 

Link from node **. Enter value in

smaller than the number of send words at the source node.

 

range ** to **

Change the number of send words or number of receive

 

 

words if the allocations are not intended. If the allocations

 

 

are intended, the data link tables can be transmitted without

 

 

making any changes.

 

 

 

 

Node XX Node size

Warning: The total node send

The total number of send and receive words exceeds

 

and receive size of ** exceeds

12,000. Controller Link Units with unit version 1.2 or later are

 

12000

required for data links with 20,000 send and receive words.

 

 

For pre-Ver. 1.2 Controller Link Units, reduce the number of

 

 

send and receive words.

 

 

 

 

 

Total Node send size of **

The total number of send and receive words exceeds

 

exceeds max 20000

20,000. Reduce the number of send and receive words to

 

 

within the maximum.

 

 

 

 

 

Total Node send size of **

The total number of send and receive words exceeds 8,000.

 

exceeds max 8000

Reduce the number of send and receive words to within the

 

 

maximum.

 

 

 

 

 

Total Node send size of **

The total number of send and receive words exceeds

 

exceeds max 62000

62,000. Reduce the number of send and receive words to

 

 

within the maximum. (The 62,000 maximum can be

 

 

exceeded by personal computer boards only.)

 

 

 

 

 

Total Node send size is 0

The number of allocated words for node ** in node No. xx is

 

 

0. Change the number of words or delete the node.

 

 

 

 

Total Node send size of **

The total number of send words for node XX exceeds 1,000.

 

exceeds max 1000

Set the number of send words to 1,000 words or less.

 

 

 

Node XX Area Overlap

Warning: Duplicated area exists

The same words have been allocated for both the Data Link

Node XX Area Conflict

in Area 1 and status area

Area 1 and status area. If the duplication is not intended,

 

 

change the settings for either area. If the duplication is

 

 

intended, the data link tables can be transmitted without

 

 

making any changes.

 

 

 

 

 

Warning: Duplicated area exists

The same words have been allocated for both the Data Link

 

in Area 2 and status area

Area 2 and status area. If the duplication is not intended,

 

 

change the settings for either area. If the duplication is

 

 

intended, the data link tables can be transmitted without

 

 

making any changes.

 

 

 

 

 

Warning: Link memory areas 1

The same area has been set for both Data Link Area 1 and

 

and 2 are both set to - [Area]

2. The same area can be set if using Controller Link Units

 

 

with unit Ver. 1.2 or later. If a pre-Ver. 1.2 Controller Link Unit

 

 

is being used, set a different area each for Area 1 and Area

 

 

2. (This message is displayed for CS/CJ-series CPU Units

 

 

only.)

 

 

 

 

 

Link memory areas 1 and 2 are

The same area has been set for both Data Link Area 1 and

 

both set to [Area]

2. Set a different area each for Area 1 and Area 2. (This mes-

 

 

sage is displayed for CS/CJ-series CPU Units only.)

 

 

 

 

Link memory areas 1 and 2 are

The same address has been set for the Data Link Area and

 

both set to [Area]

the area in which both Area 1 and Area 2 are set. Reset the

 

 

addresses so that no duplication occurs. (This message is

 

 

displayed for CS/CJ-series CPU Units only.)

 

 

 

 

 

The XX symbol refers to the corresponding node address. The two asterisks (**) refer to the corresponding area type, address, and number of words.