Omron CS1W-CLK21-V1 Handling Precautions, Replacing the Unit, Bit address Unit, Word Unit

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 347
Image 347

Handling Precautions

Section 9-6

9-6 Handling Precautions

The Controller Link Unit is a Network device. If the Unit is damaged, it will effect the entire Network, so always ensure repairs are undertaken immedi- ately. We recommend that you have a spare Controller Link Unit on hand so that repairs may be conducted quickly.

9-6-1 Replacing the Unit

Observe the following precautions when replacing the Unit.

Always turn OFF the power before replacing the Unit.

Check that the new Unit is not faulty.

If you suspect that a poor connection is the cause of a malfunction, clean the connectors using a clean, soft cloth and industrial-grade alcohol. Remove any lint or threads left from the cloth, and remount the Unit.

When returning a faulty Unit for repairs, always attach a detailed fault report to the Unit and return to you nearest OMRON outlet as listed at the back of this manual.

Note 1. The DM Parameter Area for Controller Link Units without “-V1” (CS1W- CLK21 and CJ1W-CLK21) and that for Controller Link Units with “-V1” (CS1W-CLK21-V1 and CJ1W-CLK21-V1) differ in the way shown below.

• Differences in Software Switches (D30000 + 100 Unit No.)

Bit address

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CS1W-CLK21

 

 

 

CS1W-CLK21-V1

 

 

 

 

CJ1W-CLK21

 

 

 

CJ1W-CLK21-V1

 

 

Bit 11

Reserved for system use (fixed at 0)

Used as the Wired Network 62 Node Enable Bit.

 

 

 

 

 

 

0: 32 nodes max.

 

 

 

 

 

 

 

 

 

1: 62 nodes max.

 

 

 

 

 

 

 

 

 

Bit 06

Reserved for system use (fixed at 0)

Used as one of the bits for specifying the data link mode. Mode

 

 

 

 

 

set to automatic setting with 1:N allocation when this bit is

 

 

 

 

 

turned ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Manual set-

0

Automatic

0

Automatic

 

 

 

 

 

 

ting

 

 

setting -

 

setting - 1:N

(Bit 05)

0

Manual set-

0

Automatic

0

 

0

0

 

 

equality lay-

allocation

 

 

ting

 

setting

 

 

 

 

 

(Bit 04)

0

1

0

 

 

1

1

 

 

out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Difference in Data Link Automatic Setting Parameters (D3000 + 100 Unit No. + 12 to 25)

Word

 

Unit

address

 

 

CS1W-CLK21

CS1W-CLK21-V1

 

 

CJ1W-CLK21

CJ1W-CLK21-V1

 

 

 

+12 to +25

Reserved for system use (fixed at 0)

Used to make parameter settings for automatic data link cre-

 

 

ation with 1:N allocation. (Only possible when automatic setting

 

 

with 1:N allocation is selected by setting software switch bits

 

 

04, 05, and 06 to 1, 0, and 1 respectively.)

Because of the differences shown above, when using a Controller Link Unit without “-V1”, if a value other than 0 is set in the above areas of the CPU Unit’s DM Parameter Area, if the Unit is Unit with “-V1”, there is a possibility of malfunction, particularly in data link operation. Therefore, before replac- ing the Unit (i.e., while the Unit without “-V1” is still mounted), check that 0 is set in all the above areas, and then set as required after the Unit has been replaced.

2.In order to prevent faulty operation be sure to turn off the power to all nodes before replacing the Unit.

324

Page 347
Image 347
Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 Handling Precautions, Replacing the Unit, Bit address Unit, Word Unit