Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1 Example Routing Table Settings, PCs

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 267
Image 267

Setting Routing Tables

Section 7-4

7-4-8 Example Routing Table Settings

This section shows examples of routing table settings.

Example 1

The example below shows local network table settings when multiple CPU

 

 

 

 

Bus Units are mounted in a single CVM1 or CV-series PLC.

 

 

 

SYSMAC NET Link System

 

 

 

 

 

 

 

 

 

Network address B

 

 

 

 

 

 

 

Controller Link System

 

 

 

 

SYSMAC BUS/2 System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network address A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS:

Power Supply Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU: CPU Unit

 

PLC

CLK SNT

RM

BSC

CPU

PS

 

SNT: SYSMAC NET Link Unit

 

 

CLK:

Controller Link Unit

 

acting as

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RM:

SYSMAC BUS/2 Remote I/O Master

 

bridge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSC: BASIC Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit number d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit number c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit number b

 

 

 

 

 

 

 

 

Local Network Table

 

Unit number a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

Loc

SIOU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Netwk

unit #

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

A

 

(d)

 

 

 

 

 

 

 

 

 

 

 

 

2

B

 

(c)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not register SYSMAC BUS/2 Master Units and BASIC Units in local net-

 

 

 

 

work tables because these Units do not connect to networks.

Example 2

The following example show the settings for a relay network table connecting

 

 

 

 

three networks.

 

 

 

 

 

 

 

 

PLC 1

Network

 

Node address a

 

 

 

 

 

PLC 2

address A

 

 

 

Node address b

 

 

 

 

Node address c

 

 

 

 

 

 

 

PLC 3

Network

 

Node address d

address B

 

 

 

 

 

 

 

 

PLC 4

 

 

Node address e

 

 

CS1-series

PCs

 

 

Node address f

 

 

 

Network

PLC 5

address C

 

 

 

Node address g

 

 

 

 

 

Relay Network Tables

No.

End

 

Relay

 

Netwk

PC ID

Netwk

Node

 

1

B

 

A

b

2

C

 

A

b

 

 

 

 

 

 

 

 

 

 

No.

End

 

Relay

 

Netwk

PC ID

Netwk

Node

 

1

C

 

B

e

 

 

 

 

 

 

 

 

 

 

No.

End

 

Relay

 

Netwk

PC ID

Netwk

Node

 

1

A

 

B

c

2

C

 

B

e

 

 

 

 

 

 

 

 

 

 

No.

End

 

Relay

 

Netwk

PC ID

Netwk

Node

 

1

A

 

B

c

 

 

 

 

 

 

 

 

 

 

No.

End

 

Relay

 

Netwk

PC ID

Netwk

Node

 

1

A

 

C

f

2

B

 

C

f

 

 

 

 

 

On closer examination of the relay network table for PLC#, we see that the relay network is B and the relay node is c when network A is the destination, and that the relay network is B and the relay node is e when network C is the destination.