Wiring

Section 3-3

PFP-100N2

PFP-100N/50N

End Plate: PFP-M (2 Plates required per Repeater Unit)

3-3 Wiring

3-3-1 Communications Cables

Using the specified twisted-pair cable, connect all nodes using the multidrop method.

Controller Link Unit

 

 

 

BD H g

 

 

 

BD L #

 

 

 

SHLD

Terminating resistance

Terminating resistance

Terminating resistance

Terminating resistance

switch (ON)

switch (OFF)

switch (OFF)

switch (ON)

Communications Cables

The following shielded twisted-pair cables should be used for Controller Link

Network connections.

Model

Manufacturer

 

 

Li2Y-FCY2 x 0.56 qmm

Kromberg & Schubert,

 

Komtec Department

 

 

1 x 2 x AWG 20PE + Tr.CUSN + PVC

Draka Cables Industrial

 

 

#9207

Belden

 

 

ESVC 0.5 x 2 C

Bando Densen Co.

 

 

ESNC0.5X2C-99-087B

Japan Electric Wire & Cable Co.

 

 

Note 1. Use the specified cable only.

2.Keep communications cables separated from power lines or a high-tension lines to prevent influences from electronic noise.