Status Area and Troubleshooting

Section 9-2

9-2-2 C200HX/HG/HE Controller Link Units

The status of the Unit and Network is indicated in the following manner in the

PLC.

Status Area

Duplicate Operating Levels/Refresh Error: AR 00

Operating level 1 Operating level 0

A bit will be turned ON (1) the next cycle when

1)The same operating level is set more than once or

2)A refresh error occurs between the Controller LInk Unit and the PLC's CPU Unit.

Routing Table Error/Unit Restart Bits: AR 01

Operating level 1 Operating level 0

Operating level 1

Operating level 0

Resets the Controller Link Unit. Turn ON (1) and then OFF (0) to reset Unit.

1: Routing table error

Network Participation Status: AR 08, AR 09, AR 12, AR 13

Operating level 0

Operating level 1

AR 08

AR 12

AR 09

AR 13

The numbers in the squares indicate node addresses. The corresponding node participation status is as follows: 0: Not part of network

1: Part of network

Communications Controller Hardware Error, EEPROM Error: AR 11, AR 15

Operating level 0

Operating level 1

AR 11

AR 15

1: Communications controller hardware error

1: EEPROM error

Service Time: AR 16, AR 17

Operating level 0

Operating level 1

AR 16

AR 17

The service time for each PLC cycle is calculated by the PLC and displayed in 0.1-ms units in 4-digit BCD.

Operating Level Connection Status, Inconsistent Network Parameters: AR 24

Operating level 1

1: Network parameters do not match

Operating level 0

Operating level 1 Operating level 0

1: Connecting to the operating level