Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 Baud Rates

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 115
Image 115

CJ-series Controller Link Units

Section 4-2

6.Only node addresses 1 through 32 can be used on networks for which 62 nodes have not been enabled.

7.The Wired Network 62 Node Enable Bit in the DM Parameter Area soft- ware switches of CS1W-CLK21-V1 and CJ1W-CLK21-V1 Units is read when the Unit is restarted.

8.The send sequence for the data link areas is determined according to the sequence of node addresses for automatically set data links.

9.Assign node addresses consecutively beginning from 01 whenever possi- ble to minimize Network construction time.

4-2-4 Baud Rates

Set the following pins for the baud rate settings (DIP switch).

 

ON

 

 

 

 

 

ON

1 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pins 1, 2: Baud rate

Note: The factory default settings are shown.

Note Always turn OFF the PLC’s power before setting the baud rate.

Baud Rate (Pins 1 and 2) Set the same baud rate for all the nodes on the Network using DIP switch pins 1 and 2 on the front of the Unit. The baud rate is set as shown below.

The maximum transmission distance will also change according to the setting.

 

Pins

 

Baud rate

Maximum

 

 

 

 

 

transmission distance

 

Pin 1

 

Pin 2

 

 

 

 

 

 

 

 

 

 

 

OFF

 

OFF

 

2 Mbps

500 m

 

 

 

 

 

 

ON

 

OFF

 

1 Mbps

800 m

 

 

 

 

 

 

OFF

 

ON

 

500 Kbps

1 km

 

 

 

 

 

 

ON

 

ON

 

Do not set.

 

 

 

 

 

 

 

Note The factory default setting is shown in bold.

Note 1. Set the same baud rate for all the nodes on the Network. Normal commu- nication cannot be performed unless the same baud rate is set for all the nodes.

2. The default setting is 2 Mbps, 500 m.

4-2-5 Terminating Resistance

Turn ON the terminating resistance using the switch on the bottom of the Unit for the Units of both ends of the Network. The terminating resistance is required at both ends of a Network to absorb unnecessary signals and reduce noise.

The Controller Link Unit has built-in terminating resistance, which can be con- nected simply by turning ON the slide switch.

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

Bottom switch

 

Terminating resistance

OFF (factory default)

 

Not connected.

 

 

 

 

ON

 

Connected.

92

Page 115
Image 115
Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual Baud Rates