Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1 Simultaneous Execution of Communications Instructions

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 216
Image 216

Using the Message Service

Section 6-3

Simultaneous Execution of Communications Instructions

C200HX/HG/HE PLCs

CS/CJ-series, CVM1, and CV-series PLCs

Controller Link Unit

 

Controller Link Unit

CPU Unit

 

 

 

CPU Unit

 

 

 

 

Instruction 1

Operating level #0

Port

Instruction 1

Port

 

Instruction 2

Instruction 2

Instruction 3

Instruction 4

Instruction 5

Instruction 6

Operating

Port

 

level #1

 

Instruction 7 Instruction 8

There is only one communications port per operat- ing level, so no more than one communications in- struction can be executed per operating level at one time. When both operating levels are used, two instructions can be executed simultaneously.

CQM1H-series PLCs

Controller Link Unit

CPU Unit

There are eight communications ports, so eight communications can be executed simultane- ously. Only one message is refreshed from the CPU Unit to the Controller Link Unit and one from the Controller Link Unit to the CPU Unit for each CPU Bus Unit service time.

Instruction 1

Port

There is only one communications port, so no more than one communications instruction can be executed at one time.