Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 170

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 193
Image 193

Introduction

Section 6-1

RECV

@RECV(98)

S

D

C

RECV receives “m” words beginning with S (the beginning word for data transmission at the destination node, M) to the words from D (the beginning word for data reception at the source node) onwards.

 

 

Source node

Destination node M

15

0

15

0

D

 

 

 

S

 

 

 

 

 

 

 

 

 

 

"m" num-

 

 

 

 

 

 

 

 

 

 

m

ber of

 

send

 

 

 

 

 

 

 

 

words

S:Destination node beginning send word

D:Source node beginning receive word

C:Source node first control data word

15 14

0

C

"m" number of send words

0000 to 03DE (Hex): 0 to 990 words

0:Source network address not specified (local network)

1:Source network address specified.

1514131211

8 7

0

C + 1 1

Number of retries

0 to F (Hex): 0 to 15 retries Direct/Indirect

0:Direct; 1: Indirect

0:Response required

1:Response not required

0:Operating level 1

1:Operating level 0

Response monitor time

00 (Hex):

2 s (for 2 Mbps)

 

4 s (for 1 Mbps)

 

8 s (for 500 Kbps)

01 to FE (Hex): 0.1 to 25.4 s (unit: 0.1 s)

FF (Hex):

No response monitoring

 

Always

" 1" for Controller Link Networks

 

15

 

 

8 7

 

0

 

 

C + 2

 

 

 

 

 

 

 

 

 

Destination (transmission source) node address (M)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Destination (transmission source) unit address

01 to 20 (Hex): 1 to 32 (or 01 to 3E (Hex): 1 to 62)

 

The range of node addresses will vary for networks

 

00 (Hex):

 

 

PLC's CPU Unit

 

 

 

other than Controller Link Networks.

 

01 to 0F (Hex): Computer (user program)

 

 

 

 

 

 

 

 

(02 to 0F (Hex) are used when

 

 

 

 

 

 

 

using Controller Link Support

 

 

 

 

 

 

 

Boards for PCI Bus only.)

 

 

10 to 1F (Hex): Unit nos. 0 to 15

 

 

FE (Hex):

 

 

Unit onnected to network

 

15

 

 

 

 

 

0

 

 

C + 3

 

 

 

 

 

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Destination network address

 

 

00 (Hex):

 

 

Local network

 

 

01 to 7F (Hex):

1 to 127

 

This setting is enabled only when Destination network address specified" is set in word C. When specifying the destination network address, set all the nodes in the routing tables. For details on the routing tables, refer to Section 7 Network Interconnections.

Note 1. When communicating in the same network with a CVM1 or CV-series PLC manufactured prior to April 1996, the local network address cannot be set to “00.” Set a number other than “00” as the local network address in the routing tables, and then specify that number.

2.With the message service, there is no guarantee that a message to a des- tination node will reach its destination. It is always possible that the mes-

170

Page 193
Image 193
Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual 170